![Trane Precedent RT-PRC005 Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/trane/precedent-rt-prc005/precedent-rt-prc005_user-manual_1149464030.webp)
30
RT-PRC005-EN
Performance
Data
(6 Ton)
Standard Efficiency
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
Table PD-27 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1 HP Standard Motor & Drive
1HP Standard Motor & High Static Drive Kit
(or 2 HP Oversized Motor & Drive)
1920
925
0.95
960
1.03
994
1.11
1026
1.19
1057
1.27
1087
1.36
1116
1.44
1144
1.52
1173
1.61
1200
1.70
2160
944
1.08
978
1.17
1010
1.26
1043
1.36
1073
1.44
1104
1.54
1133
1.63
1162
1.72
1189
1.81
1216
1.91
2400
964
1.22
998
1.32
1030
1.42
1063
1.53
1092
1.63
1123
1.73
1151
1.83
1179
1.93
1206
2.03
1233
2.13
2640
986
1.39
1019
1.49
1051
1.60
1082
1.71
1112
1.81
1141
1.92
1169
2.03
1198
2.15
1225
2.26
—
—
2880
1011
1.58
1043
1.69
1073
1.79
1103
1.90
1133
2.02
1161
2.13
1190
2.26
—
—
—
—
—
—
2 HP Oversized Motor & Drive
Table PD-27 — Belt Drive Evaporator Fan Performance — 6-Ton — TSC072A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1
)
1920
—
—
—
—
573
0.34
630
0.41
680
0.48
726
0.55
769
0.62
811
0.70
851
0.78
889
0.87
2160
—
—
548
0.35
602
0.42
656
0.50
706
0.58
751
0.65
792
0.73
832
0.81
871
0.90
908
0.99
2400
—
—
584
0.45
635
0.52
682
0.60
732
0.69
777
0.77
818
0.86
856
0.95
893
1.04
930
1.13
2640
569
0.47
621
0.56
670
0.64
715
0.72
758
0.81
802
0.91
845
1.01
883
1.10
919
1.20
953
1.29
2880
612
0.60
660
0.69
706
0.78
749
0.86
789
0.96
830
1.06
870
1.16
909
1.27
945
1.37
979
1.48
For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Table PD-28 — Belt Drive Evaporator Fan Performance — 6-Ton — TSC072A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
1920
—
—
565
0.31
627
0.39
679
0.45
726
0.52
771
0.60
814
0.69
857
0.77
899
0.85
939
0.93
2160
566
0.35
609
0.41
663
0.48
716
0.57
762
0.64
804
0.72
843
0.80
883
0.90
922
0.99
960
1.08
2400
619
0.47
660
0.54
701
0.60
751
0.69
798
0.78
839
0.87
877
0.95
914
1.04
950
1.14
984
1.24
2640
672
0.61
710
0.68
745
0.76
788
0.83
833
0.93
875
1.04
914
1.13
949
1.22
984
1.31
1016
1.42
2880
726
0.77
762
0.86
795
0.94
828
1.02
869
1.11
911
1.21
950
1.33
986
1.44
1019
1.53
1051
1.63
2-HP Oversized
Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop
due to other options/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range
of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be
affected.
1-HP Standard Motor
& Field Supplied
Low Static Drive (1
)
1HP Standard Motor & High Static Drive
Kit(or 2 HP Oversized Motor & Drive)
Table PD-28 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard
1-HP Standard Motor & High Static Drive Kit
Motor& Drive
(or 2 HP oversized Motor& Drive)
1920
978
1.02
1015
1.11
1051
1.20
1086
1.30
1118
1.39
1150
1.49
1180
1.58
1209
1.68
1236
1.77
1263
1.86
2160
996
1.17
1034
1.27
1069
1.36
1103
1.46
1136
1.56
1169
1.67
1199
1.77
1229
1.88
1258
1.98
—
—
2400
1020
1.35
1055
1.45
1089
1.55
1122
1.66
1154
1.76
1186
1.86
1216
1.97
1246
2.08
1276
2.20
—
—
2640
1049
1.53
1081
1.65
1113
1.76
1144
1.87
1176
1.98
1207
2.10
1237
2.21
—
—
—
—
—
—
2880
1081
1.74
1112
1.86
1141
1.97
1170
2.10
1199
2.22
—
—
—
—
—
—
—
—
—
—
2-HP Oversized Motor & Drive