39
RT-PRC005-EN
Table PD-44 — Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1
)
1600
707
0.35
774
0.42
837
0.50
898
0.57
953
0.65
1001
0.72
1045
0.80
1087
0.87
1129
0.95
1168
1.03
1800
778
0.48
840
0.56
897
0.64
953
0.72
1008
0.81
1058
0.89
1102
0.98
1143
1.06
1181
1.15
1219
1.23
2000
850
0.65
908
0.73
961
0.81
1012
0.90
1062
1.00
1111
1.09
1157
1.19
1198
1.28
1237
1.37
1274
1.47
2200
923
0.84
978
0.93
1028
1.02
1075
1.12
1120
1.22
1166
1.32
1211
1.43
—
—
—
—
—
—
2400
997
1.07
1049
1.17
1096
1.27
1140
1.37
1183
1.48
—
—
—
—
—
—
—
—
—
—
For Standard Evaporator Fan Speed (RPM), reference Table PD-50.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.
Trane’s factory supplied motors, in commercial
equipment, are definite purpose motors,
specifically designed and tested to operate
reliably and continuously at all cataloged
conditions. Using the full horsepower range of our
fan motors as shown in our tabular data will not
result in nuisance tripping or premature motor
failure. Our product’s warranty will not be
affected.
Table PD-44 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor
1600
1206
1.12
1241
1.20
1275
1.28
1306
1.37
1338
1.46
1800
1256
1.32
1291
1.41
1326
1.50
—
—
—
—
2000
—
—
—
—
—
—
—
—
—
—
2200
—
—
—
—
—
—
—
—
—
—
2400
—
—
—
—
—
—
—
—
—
—
Performance
Data
(5 Ton)
High Efficiency
Table PD-45— Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Horizontal Airflow — Dehumidification (Hot Gas Reheat)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1000
507
0.11
599
0.16
671
0.21
735
0.26
792
0.31
843
0.37
889
0.42
931
0.48
971
0.54
1007
0.59
1200
570
0.17
654
0.23
727
0.28
787
0.34
843
0.40
895
0.46
942
0.52
986
0.59
1026
0.66
1064
0.73
1400
638
0.25
711
0.31
782
0.38
844
0.44
896
0.51
946
0.58
993
0.65
1037
0.72
1078
0.79
1117
0.86
1600
707
0.35
774
0.42
837
0.50
898
0.57
953
0.65
1001
0.72
1045
0.80
1087
0.87
1129
0.95
1168
1.03
Trane’s factory supplied motors, in commercial equipment,
are definite purpose motors, specifically designed and
tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan
motors as shown in our tabular data will not result in
nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.
Table PD-45 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
1000
1042
0.65
1078
0.70
1110
0.76
1142
0.82
1175
0.89
1200
1099
0.80
1133
0.86
1166
0.93
1197
0.99
1227
1.06
1400
1153
0.94
1188
1.02
1221
1.10
1253
1.18
1284
1.27
1600
1206
1.12
1241
1.20
1275
1.28
1306
1.37
1338
1.46
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR008A Required.
2. BAYLSDR008A Required.
1-HP Standard Motor & Low
Static Drive Accessory Kit (1
)
1-HP Standard Motor & Low
Static Drive Accessory Kit (2)
1-HP Standard Motor & Drive