Table PD-21 — Belt Drive Evaporator Fan Performance — 3 Ton — TSC036A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor
& Field Supplied
Low Static Drive (1
)
1-HP Standard Motor & Drive
960
—
—
528
0.12
599
0.16
658
0.20
713
0.24
763
0.29
810
0.33
855
0.38
898
0.43
939
0.49
1080
—
—
557
0.15
625
0.19
685
0.24
738
0.28
786
0.33
832
0.38
876
0.43
917
0.48
957
0.54
1200
—
—
588
0.19
652
0.23
712
0.28
764
0.33
811
0.38
856
0.43
898
0.48
939
0.54
978
0.59
1320
552
0.18
622
0.23
681
0.27
738
0.32
790
0.38
838
0.44
882
0.49
923
0.55
962
0.60
1000
0.66
1440
588
0.23
657
0.28
713
0.33
765
0.37
817
0.43
865
0.50
909
0.56
949
0.62
987
0.68
1024
0.74
For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Table PD-21 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
960
978
0.54
1016
0.60
1052
0.66
1086
0.72
1120
0.78
1080
995
0.59
1033
0.65
1069
0.71
1103
0.78
1136
0.84
1200
1015
0.65
1051
0.71
1086
0.77
1120
0.84
1154
0.91
1320
1036
0.72
1072
0.78
1106
0.85
1138
0.91
1171
0.98
1440
1060
0.80
1094
0.86
1128
0.93
1160
1.00
1192
1.07
Trane’s factory supplied motors, in commercial
equipment, are definite purpose motors,
specifically designed and tested to operate
reliably and continuously at all cataloged
conditions. Using the full horsepower range of our
fan motors as shown in our tabular data will not
result in nuisance tripping or premature motor
failure. Our product’s warranty will not be
affected.
1-HP Standard Motor &
Field Supplied High Static Drive (2)
Table PD-22 — Belt Drive Evaporator Fan Performance — 3 Ton — TSC036A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1
)
960
—
—
588
0.15
661
0.19
725
0.24
782
0.29
832
0.35
878
0.40
919
0.46
958
0.51
996
0.56
1080
531
0.13
622
0.18
694
0.24
756
0.29
813
0.34
864
0.40
910
0.46
954
0.52
993
0.59
1031
0.65
1200
570
0.17
654
0.23
727
0.28
787
0.34
843
0.40
895
0.46
942
0.52
986
0.59
1026
0.66
1064
0.73
1320
610
0.22
687
0.28
760
0.34
821
0.40
875
0.46
925
0.53
973
0.59
1017
0.66
1058
0.73
1095
0.81
1440
651
0.27
723
0.33
793
0.40
855
0.47
908
0.53
956
0.60
1003
0.67
1047
0.75
1088
0.82
1127
0.89
For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Table PD-22 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
960
1032
0.62
1066
0.67
1101
0.73
1133
0.79
1166
0.86
1080
1065
0.70
1099
0.76
1132
0.82
1164
0.89
1194
0.95
1200
1099
0.80
1133
0.86
1166
0.93
1197
0.99
1227
1.06
1320
1132
0.88
1167
0.96
1200
1.04
1230
1.11
1261
1.19
1440
1164
0.97
1199
1.05
1232
1.14
1263
1.22
1294
1.30
1-HP Standard Motor &
Field Supplied High Static Drive (2)
1-HP Standard Motor &
Field Supplied High Static Drive
(2)
Trane’s factory supplied motors, in commercial
equipment, are definite purpose motors,
specifically designed and tested to operate
reliably and continuously at all cataloged
conditions. Using the full horsepower range of our
fan motors as shown in our tabular data will not
result in nuisance tripping or premature motor
failure. Our product’s warranty will not be
affected.
Performance
Data