74

RT-PRC005-EN

Mechanical
Specifications

24-volt electromechanical control circuit
shall include control transformer and
contactor pressure lugs for power
wiring. Units shall have single point
power entry as standard.

Accessories/Options

Electric Heaters

 — Factory or field-

installed electric heat modules shall be
available for installation within basic
unit. Electric heater elements shall be
constructed of heavy-duty nickel
chromium elements internally delta
connected for 240 volt, wye connected
for 480 and 600 volt. Staging shall be
achieved through the unitary control
processor (UCP). Each heater package
shall have automatically reset high limit
control operating through heating
element contactors. All heaters shall be
individually fused from the factory,
where required, and shall meet all NEC
and CEC requirements when properly
installed. Power assemblies shall provide
single-point connection. Electric heat
modules shall be UL listed or CSA
certified.

Roof Curb 

 

The roof curb shall be

designed to mate with the unit’s
downflow supply and return and provide
support and a water tight installation
when installed properly. The roof curb
design shall allow field-fabricated
rectangular supply/return ductwork to be
connected directly to the curb. Curb
design shall comply with NRCA
requirements. Curb shall be shipped
knocked down for field assembly and
shall include wood nailer strips.

Economizer 

 

This accessory shall be

either field or factory-installed and shall
be available with or without barometric
relief. The assembly includes fully
modulating 0-100 percent motor and
dampers, minimum position setting,
preset linkage, wiring harness with plug,
spring return actuator and fixed dry bulb
control. The barometric relief shall
provide a pressure operated damper that
shall be gravity closing and shall prohibit
entrance of outside air during the
equipment “off” cycle. Optional solid
state or differential enthalpy control shall
be available for either factory or field
installation. The  factory-installed
economizer arrives in the shipping
position and shall be moved to the

operating position by the installing
contractor.

Powered Exhaust

 — The field installed

powered exhaust, available for 6-10 ton
units, shall provide exhaust of return air,
when using an economizer, to maintain
better bulding pressurization.

Remote Potentiometer

 —

 

The minimum

position setting of the economizer shall
be adjusted with this accessory.

Manual Outside Air Damper

 — Factory

or field-installed rain hood and screen
shall provide up to 50 percent outside air.

Motorized Outside Air Dampers

 —

Factory or field-installed manually set
outdoor air dampers shall provide up to
50 percent outside air. Once set, outdoor
air dampers shall open to set position
when indoor fan starts. The damper shall
close to the full closed position when
indoor fan shuts down.

Discharge Air Sensing 

 — This factory or

field-installed option provides true
discharge air sensing in heating models.
This sensor is a status indicator readable
through Tracer® or Tracker®.  This option
is available for microprocessor
controlled units.

Oversized Motors

 — Factory or field-

installed direct drive oversized motors
shall be available for high static
applications.

Through the Base Electrical  Access

 

An electrical service entrance shall be
factory provided allowing electrical
access for both control and main power
connections inside the curb and through
the base of the unit. Option will allow for
field installation of liquid-tight conduit
and an external field-installed disconnect
switch.

Through the Base Electrical with
Disconnect Switch

 — Factory-installed 3-

pole, molded case, disconnect switch
with provisions for through the base
electrical connections are available. The
disconnect switch will be installed in the
unit in a water tight enclosure with
access through a swinging door. Factory
wiring will be provided from the switch
to the unit high voltage terminal block.
The switch will be UL/CSA agency
recognized. Note: The disconnect switch
will be sized per NEC and UL guidelines
but will not be used in place of unit
overcurrent protection.

Through the Base Electrical with Circuit
Breaker

 

— This option is a factory-

installed, thermal magnetic, molded
case, HACR Circuit Breaker with
provisions for through the base electrical
connections. The circuit breaker will be
installed in a water tight enclosure in the
unit with access through a swinging
door. Factory wiring will be provided
from the switch to the unit high voltage
terminal block. The circuit breaker will
provide overcurrent protection, be sized
per NEC and UL guidelines, and be
agency recognized by UL/CSA.

Powered or Unpowered Convenience
Outlet

 

— This factory-installed option is a

GFCI, 120v/15amp, 2 plug, convenience
outlet, either powered or unpowered.
When the convenience outlet is
powered, a service receptacle disconnect
will be available. The convenience outlet
is powered from the line side of the
disconnect or circuit breaker, and
therefore will not be affected by the
position of the disconnect or circuit
breaker. This option can only be ordered
when the Through the Base Electrical
with either the Disconnect Switch or
Circuit Breaker option is ordered.

Clogged Filter/Fan Failure Switch

 — A

dedicated differential pressure switch is
available, factory-installed, to achieve
active fan failure indication and/or
clogged filter indication. These
indications will be registered with either
a zone sensor with status indication
lights or an Integrated Comfort™
System. This option is available for
microprocessor controlled units.

Reference or Comparative Enthalpy

 —

Factory-installed Reference or
Comparative Enthalpy option shall be
available when a factory-installed
Economizer is ordered. This option is
available for microprocessor controlled
units.

High Pressure Cutout

 — This factory-

installed option is offered for units that
do not have High Pressure cutout as
standard. All 3-phase units with scroll
compressors include High Pressure
Cutout as standard.

Hinged Access Doors

 — Sheet metal

hinges are available factory-installed on
the Filter/Evaporator, Supply Fan/Heat,
and the Compressor/Control Access
Doors.

Содержание Precedent RT-PRC005

Страница 1: ...Packaged Cooling with ElectricHeatRooftopUnits Precedent 3 10T ons 60 Hz RT PRC005 EN March 2003...

Страница 2: ...r applications and for the more sophisticated ReliaTel microprocessor controls In addition to controls Precedent offers many other outstanding features and option choices With its sleek compact cabine...

Страница 3: ...Considerations Selection Procedure Model Number Description General Data Performance Data Cooling Performance Fan Performance Heat Performance Controls Electric Power Dimension andWeights Mechanical...

Страница 4: ...hat s easy to clean and reversible to allow installation of drain trap on either side of the unit Through the Base Condensate Every unit includes provisions for through the base condensate drain conne...

Страница 5: ...temperature Improves quality and reliability through the use of time tested microprocessor controls and logic Prevents the unit from short cycling considerably improving compressor life Ensures that t...

Страница 6: ...Comfort System to indicate a dirty filter or a fan that s not working The field installation charges for these valuable feedback devices often eliminate them from consideration Factory installation c...

Страница 7: ...ves a 100 unit run test before leaving the production line to make sure it lives up to rigorousTrane requirements We test designs at our factory not on our customers QualityAnd ReliabilityTesting All...

Страница 8: ...ection also increases opening the dampers and relieving the conditioned space NOTE THE EFFECTIVENESS OF BAROMETRIC RELIEF DAMPER DURING ECONOMIZING OPERATION IS SYSTEM RELATED PRESSURE DROP OFTHE RETU...

Страница 9: ...r Size 6 kW 0 05 wg fromTable PD 51 Total Static Pressure 0 67 wg Note The Evaporator Fan Performance Table PD 20 has deducted the pressure drop for a 1 in filter already in the unit see note belowTab...

Страница 10: ...or 0 No Smoke Detector A ReturnAir Smoke Detector B Supply Air Smoke Detector C Supply and Return Air Smoke Detectors DIGIT 25 Monitoring Controls 0 No Monitoring Control 1 Clogged Filter Switch 2 Fan...

Страница 11: ...1 1 1 1 Diameter xWidth in 10 x 10 11 x 11 11 x 11 11 x 11 11 x 11 12x11 DriveType No Speeds Direct 2 Direct 2 Direct 2 Direct 2 Direct 2 Direct 2 No Motors 1 1 1 1 1 1 Motor HP Standard Oversized 33...

Страница 12: ...ed No Motors 1 1 1 1 1 Motor HP Standard Oversized 1 00 2 0012 2 00 3 00 2 00 3 00 2 00 3 00 3 00 5 00 Motor RPM Standard Oversized 1750 1750 1750 1750 1750 3450 Motor Frame Size 56 56 56 56 56 Filter...

Страница 13: ...sized 48 48 48 48 48 48 48 48 Belt Drive Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal No Used 1 1 1 Diameter xWidth in 11 x 11 11 x 11 11 x 11 DriveType No Speeds Belt Variable Speed 6...

Страница 14: ...3 00 5 00 Motor RPM Standard Oversized 1750 1750 1750 1750 3450 Motor Frame Size 56 56 56 56 Filters Type Furnished 9 Throwaway Throwaway Throwaway Throwaway No Size Recommended in 4 16 x 25 x 2 4 20...

Страница 15: ...red indoor fan heat To obtain net cooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 1 Gross Cooling Capacities MBH 3 Ton Single Three Phase TSC036A1 A3...

Страница 16: ...red indoor fan heat To obtain net cooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 4 Gross Cooling Capacities MBH 5 Ton Single Three Phase TSC060A1 A3...

Страница 17: ...To obtain net cooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC SensibleHeatCapacity Table PD 6 Gross Cooling Capacities MBH 7 Ton Three Phase Single Compressor TSC090A3 A4 AW AK Ambi...

Страница 18: ...105 2 105 2 105 2 105 2 107 8 95 4 NOTES 1 All capacities shown are gross and have not considered indoor fan heat To obtain net cooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC Sensib...

Страница 19: ...06 7 106 7 106 7 106 7 116 9 80 7 90 124 5 124 5 124 9 124 9 128 4 91 9 122 9 122 9 122 6 122 6 127 2 95 7 119 3 119 3 119 3 119 3 123 3 97 3 114 3 114 3 114 3 114 3 118 3 99 2 75 114 1 106 4 120 6 73...

Страница 20: ...nsidered indoor fan heat To obtain net cooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 10 Gross Cooling Capacities MBH 3Ton THC036A1 A3 A4 AW AmbientT...

Страница 21: ...dered indoor fan heat To obtain net cooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 13 Gross Cooling Capacities MBH 5Ton Three Phase THC060A3 A4 AW Am...

Страница 22: ...6 5 50 7 50 7 54 9 43 7 61 1 34 8 48 1 48 1 51 5 41 9 57 4 33 0 90 58 8 58 8 61 5 54 4 68 1 45 3 56 3 56 3 58 5 52 7 64 8 43 6 53 7 53 7 55 3 50 9 61 3 41 9 51 0 51 0 52 0 49 1 57 5 40 1 75 56 8 46 5...

Страница 23: ...heat To obtain net cooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC SensibleHeatCapacity Table PD 16 Gross Cooling Capacities MBH 7 Ton Three Phase THC092A3 A4 AW AmbientTemperature F...

Страница 24: ...ooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC SensibleHeatCapacity Table PD 18 Gross Cooling Capacities MBH 10Ton Three Phase THC120A3 A4 AW AmbientTemperature F 85 95 105 115 Enter...

Страница 25: ...6 96 2 80 9 107 6 64 0 90 109 9 109 9 113 9 103 3 126 4 86 1 105 6 105 6 108 7 100 5 120 7 83 4 101 1 101 1 101 1 101 1 114 5 80 6 96 2 96 2 97 5 92 3 107 9 77 6 75 104 9 87 8 117 1 67 4 130 2 46 6 99...

Страница 26: ...0 99 0 41 0 91 0 47 1080 0 78 0 38 0 55 0 29 0 96 0 43 0 87 0 39 1140 0 74 0 39 0 47 0 29 0 93 0 44 0 82 0 40 3 TSC036A 1200 0 71 0 40 0 39 0 30 0 89 0 45 0 79 0 41 Downflow 1260 0 65 0 41 0 31 0 30 0...

Страница 27: ...not be affected 1 HPStandardMotor Field Supplied High Static Drive 2 Table PD 22 Belt Drive Evaporator Fan Performance 3 Ton TSC036A3 A4 AW Horizontal Airflow External Static Pressure Inches ofWater...

Страница 28: ...229 1 29 1920 1172 1 23 1205 1 31 1236 1 39 Table PD 24 Continued External Static Pressure Inches ofWater 1 10 1 20 1 30 1 40 1 50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1 HPStandardMotor Drive 1...

Страница 29: ...RPM BHP RPM BHP RPM BHP 1 HPStandardMotor Drive 1600 1117 0 97 1150 1 04 1183 1 11 1215 1 18 1244 1 25 1800 1167 1 16 1 199 1 24 1230 1 31 1259 1 39 1289 1 47 2000 1216 1 37 1249 1 47 2200 2400 Table...

Страница 30: ...2 HPFanMotorHeat MBH 3 000xFanBHP 5000 1 FieldSuppliedFanSheaveAK84andBeltAX34required Table PD 28 Belt Drive Evaporator Fan Performance 6 Ton TSC072A3 A4 AW Horizontal Airflow External Static Pressu...

Страница 31: ...torsas shown in our tabular data will not result in nuisance tripping or premature motor failure Ourproduct swarrantywillnotbeaffected Table PD 30 Belt Drive Evaporator Fan Performance 6 Ton TSC072 AK...

Страница 32: ...sance tripping or premature motor failure Ourproduct swarrantywillnotbeaffected Table PD 32 Continued External Static Pressure Inches ofWater 1 10 1 20 1 30 1 40 1 50 1 60 1 70 1 80 1 90 2 00 CFM RPM...

Страница 33: ...shown in our tabular data will not result in nuisance tripping or premature motor failure Ourproduct swarrantywillnotbeaffected Table PD 34 Continued External Static Pressure Inches ofWater 1 10 1 20...

Страница 34: ...nsareincludedinpressuredropdata RefertoTablePD 54todetermineadditionalstaticpressuredrop duetootheroptions accessories 3 HPFanMotorHeat MBH 2 900xFanBHP 475 5 HPFanMotorHeat MBH 2 950xFanBHP 470 1 Fie...

Страница 35: ...1 20 960 0 79 0 36 0 56 0 28 0 94 0 38 0 82 0 35 1020 0 74 0 37 0 54 0 28 0 90 0 39 0 82 0 36 1080 0 70 0 38 0 49 0 29 0 87 0 41 0 79 0 38 1140 0 66 0 39 0 42 0 29 0 82 0 43 0 74 0 40 3 THC036A 1200 0...

Страница 36: ...s warranty will not be affected 1 HPStandardMotor Field Supplied High Static Drive 2 Table PD 39 Belt Drive Evaporator Fan Performance 3 Ton THC036A3 A4 AW Horizontal Airflow External Static Pressure...

Страница 37: ...1211 1 25 1241 1 32 1920 1186 1 26 1218 1 34 1249 1 42 Table PD 41 Belt Drive Evaporator Fan Performance 4 Ton THC048A3 A4 AW Horizontal Airflow External Static Pressure Inches ofWater 10 20 30 40 50...

Страница 38: ...00 1226 1 48 2400 PD 43 Continued External Static Pressure Inches ofWater 1 10 1 20 1 30 1 40 1 50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1 HPStandardMotor Drive 1000 985 0 56 1021 0 62 1058 0 68...

Страница 39: ...5 Ton THC060A3 A4 AW Horizontal Airflow Dehumidification Hot Gas Reheat External Static Pressure Inches ofWater 10 20 30 40 50 60 70 80 90 1 00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM...

Страница 40: ...0 1137 1 70 1168 1 81 1201 1 92 1232 2 03 1261 2 14 1291 2 26 2640 1065 1 59 1097 1 71 1129 1 82 1161 1 93 1192 2 05 1223 2 16 1252 2 27 2880 1099 1 80 1130 1 93 1159 2 05 1188 2 18 1217 2 30 2 HP Ove...

Страница 41: ...tabular data will not result in nuisance tripping or premature motor failure Ourproduct swarrantywillnotbeaffected Table PD 49 Belt Drive Evaporator Fan Performance 7 Ton THC092A3 A4 AW Horizontal Ai...

Страница 42: ...rsas shown in our tabular data will not result in nuisance tripping or premature motor failure Ourproduct swarrantywillnotbeaffected Table PD 51 Belt Drive Evaporator Fan Performance 8 Ton THC102A3 A4...

Страница 43: ...fanmotorsas shown in our tabular data will not result in nuisance tripping or premature motor failure Ourproduct swarrantywillnotbeaffected Table PD 53 Continued External Static Pressure Inches ofWate...

Страница 44: ...own in our tabular data will not result in nuisance tripping or premature motor failure Ourproduct swarrantywillnotbeaffected Table PD 55 Belt Drive Evaporator Fan Performance 10 Ton THC120A3 A4 AW Ho...

Страница 45: ...PD 58 Oversized Motor Drive Sheave Fan Speed Rpm Unit 6Turns 5Turns 4Turns 3Turns 2Turns 1Turn Tons Model No Open Open Open Open Open Open Closed 6 T C072A3 A4 AW N A 958 1022 1086 1150 1214 1278 7 TS...

Страница 46: ...045 053 1800 09 2000 0 06 10 0 10 0 18 0 07 0 18 0 02 056 070 083 2200 12 2400 0 09 14 0 14 0 26 0 10 0 26 0 04 081 100 120 1920 0 04 0 07 0 10 0 01 0 06 0 02 0 02 0 011 0 021 6 T C072A 2400 0 06 0 09...

Страница 47: ...14 30 48 82 8 70 29 70 7 50 25 61 2 3 25 11 10 3 25 11 10 TSC060AK 10 90 37 23 2 5 45 18 61 5 45 18 61 14 4 49 18 2 7 20 24 59 7 20 24 59 9 00 30 73 1 9 00 30 73 T C072A3 A4 AW 18 00 61 45 1 18 00 61...

Страница 48: ...2 16 9 16 6 2200 16 8 16 6 16 4 16 2 16 0 15 7 15 4 2400 15 6 15 4 15 2 15 1 14 9 14 6 14 3 10Tons 35 40 45 50 55 60 65 2000 26 0 26 5 26 9 27 4 27 9 28 3 28 6 2400 23 5 24 1 24 7 25 3 25 9 26 4 26 9...

Страница 49: ...ven day programming Keyboard selection of Heat Cool Fan Auto or On All programmable sensors have System On Heat Cool Service LED indicators as standard Night Setback Sensors have one 1 Occupied one 1...

Страница 50: ...53 47 3 60 49 0 60 N A N A TSC060A3 187 253 31 5 50 33 2 50 30 3 45 5 TSC060A4 414 506 16 0 25 16 3 25 15 6 25 TSC060AW 517 633 12 2 15 12 8 20 11 8 15 TSC060AK 342 418 19 6 30 TSC072A3 187 253 32 7 5...

Страница 51: ...3 29 4 45 31 5 50 N A N A THC048A3 187 253 21 2 30 23 3 35 22 6 35 4 THC048A4 414 506 11 0 15 12 6 15 11 8 15 THC048AW 517 633 8 3 15 9 1 15 8 5 15 THC060A1 187 253 39 5 60 41 2 60 N A N A THC060A3 18...

Страница 52: ...9 50 60 52 5 59 5 60 60 BAYHTRR306A 4 5 6 0 1 31 5 31 5 50 50 33 2 33 2 50 50 BAYHTRR312A 9 0 12 0 2 39 0 43 9 50 50 41 1 46 0 50 50 5 TSC060A3 BAYHTRR318A 13 1 17 4 2 53 1 60 1 60 70 55 3 62 3 60 70...

Страница 53: ...0 BAYHTRR406A 6 0 1 12 8 20 14 4 20 4 TSC048A4 BAYHTRR412A 12 0 2 20 1 25 22 1 25 BAYHTRR418A 17 4 2 28 3 30 30 3 35 BAYHTRR406A 6 0 1 16 0 25 16 3 25 BAYHTRR412A 12 0 2 21 6 25 22 0 25 5 TSC060A4 BAY...

Страница 54: ...24 3 25 BAYHTRRW23A 23 0 2 30 3 35 31 0 35 BAYHTRSW09A 9 0 1 13 0 20 14 0 20 6 TSC072AW BAYHTRSW18A 18 0 1 23 8 25 24 8 25 BAYHTRSW27A 27 0 2 34 6 35 35 6 40 BAYHTRSW36A 36 0 2 45 4 50 46 4 50 BAYHTR...

Страница 55: ...306A 4 5 6 0 1 25 3 25 3 35 35 4 TSC048A3 BAYHTRR312A 9 0 12 0 2 37 5 42 4 40 45 BAYHTRR318A 13 1 17 4 2 51 6 58 6 60 60 BAYHTRR306A 4 5 6 0 1 30 3 30 3 45 45 BAYHTRR312A 9 0 12 0 2 37 5 42 4 45 45 5...

Страница 56: ...0 23 3 25 1 35 35 4 THC048A3 BAYHTRR312A 9 0 12 0 2 35 8 40 6 40 45 38 4 43 3 40 45 BAYHTRR318A 13 1 17 4 2 49 9 56 9 50 60 52 5 59 5 60 60 BAYHTRR306A 4 5 6 0 1 30 0 30 0 45 45 31 7 31 7 45 45 BAYHTR...

Страница 57: ...HTRR412A 12 0 2 21 6 25 22 0 25 BAYHTRR418A 17 4 2 29 8 30 30 1 35 BAYHTRR423A 23 0 2 38 3 40 38 6 40 BAYHTRS409A 9 0 1 17 5 25 18 1 25 6 THC072A4 BAYHTRS418A 18 0 1 30 3 35 31 0 35 BAYHTRS427A 27 0 2...

Страница 58: ...1 11 8 15 12 4 15 BAYHTRRW12A 12 0 2 17 1 20 17 8 20 5 THC060AW BAYHTRRW18A 17 4 2 23 6 25 24 3 25 BAYHTRRW23A 23 0 2 30 3 35 31 0 35 BAYHTRSW09A 9 0 1 13 5 20 14 3 20 6 THC072AW BAYHTRSW18A 18 0 1 2...

Страница 59: ...ic Heat Single Point Connection Optional Belt Drive High Efficiency Belt Drive Indoor Motor To Use Heater Heater Control Max Fuse Size Or Tons With Model No kW Rating1 Stages MCA Max Circuit Breaker2...

Страница 60: ...72AK 1 380 3 2 0 4 9 35 0 T C090A3 1 208 230 3 2 00 6 30 48 00 1 208 230 3 3 00 9 40 83 00 T C090A4 1 460 3 2 00 3 10 24 00 1 460 3 3 00 4 60 42 00 T C090AW 1 575 3 2 00 2 50 18 20 1 575 3 3 00 3 70 3...

Страница 61: ...1 70 1 54 3 60 TSC072AK 1 380 3 6 3450 12 2 70 1 1 75 2 5 7 7 TSC090A3 1 208 230 3 7 5 3450 26 0 172 1 1 70 3 85 9 30 TSC090A4 1 460 3 7 5 3450 13 6 90 1 1 70 2 50 5 80 TSC090AW 1 575 3 7 5 3450 10 9...

Страница 62: ...8 230 3 5 7 3450 20 7 156 1 1 70 3 85 9 30 6 THC072A4 1 460 3 5 7 3450 10 75 1 1 70 2 50 5 80 THC072AW 1 575 3 5 7 3450 8 2 54 1 1 70 1 54 3 60 THC092A3 2 208 230 3 3 5 3 3 3450 12 4 12 4 88 88 1 1 70...

Страница 63: ...OTHERS ROOFTOP UNIT ZONE SENSOR OR THERMOSTAT Zone Sensors Typical Number OfWires A Manual Changeover 4 Manual Auto Changeover 5 Manual Auto Changeover with Status Indication LED s 10 Programmable Nig...

Страница 64: ...64 RT PRC005 EN Dimensional Data All dimensions are in inches millimeters 5Tons High Efficiency 3 5Tons Standard Efficiency 3 and 4Tons High Efficiency 3 5Tons...

Страница 65: ...5 RT PRC005 EN Dimensional Data All dimensions are in inches millimeters HorizontalAirflow Supply Return DownflowAirflow Supply Return Through the Base Utilities Unit Clearance and Roof Opening 3 5Ton...

Страница 66: ...66 RT PRC005 EN Dimensional Data All dimensions are in inches Downflow Duct Connections Field Fabricated 3 5Tons 37 1 8 928 MM...

Страница 67: ...67 RT PRC005 EN 6 10Tons Dimensional Data All dimensions are in inches 6Tons Standard and High Efficiency 7 Tons Standard Efficiency 7 Tons High Efficiency 8 and 10Tons Standard and High Efficiency...

Страница 68: ...Tons Dimensional Data All dimensions are in inches 6 10Tons DownflowAirflow Supply and Return Through the Base Utilities 6 10Tons HorizontalAirflow Supply and Return 6 10Tons Unit Clearance and Roof O...

Страница 69: ...69 RT PRC005 EN 6 10Tons Dimensional Data All dimensions are in inches 6 10Tons Roof Curb ALL FLANGES 1 1 4 31 MM 6 10Tons Downflow Duct Connections Field Fabricated...

Страница 70: ...s Accessories Dimensional Data All dimensions are in inches Economizer Manual or Motorized FreshAir Damper See Page 65 for Through the Base Utilities Information Barometric Relief Damper Hood Swing Di...

Страница 71: ...dimensions are in inches 6 10Tons Economizer and Barometric Relief Damper Hoods 6 10Tons Power Exhaust 6 10Tons Swing Diameter for Hinged Door s Option 6 10Tons Options Accessories See Page 68 for Th...

Страница 72: ...294 233 159 207 39 22 TSC120A 1052 909 306 241 164 197 40 21 10 THC120A 1125 982 323 253 178 229 39 22 NOTES 1 Corner weights are given for information only 2 Weights are approximate TableW 2 Factory...

Страница 73: ...plate voltage Crankcase heater internal temperature and current sensitive motor overloads shall be included for maximum protection Compressors shall have internal spring isolation and sound muffling t...

Страница 74: ...r is a status indicator readable throughTracer orTracker This option is available for microprocessor controlled units Oversized Motors Factory or field installed direct drive oversized motors shall be...

Страница 75: ...energy savings potential than the standard dry bulb control This is due to the additional wet bulb sensing capability This option shall be available for microprocessor controlled units It can be fiel...

Страница 76: ...com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice Literature Order Number File Number Supersedes Stoc...

Отзывы: