14
RT-PRC005-EN
General
Data
(6 - 10 Ton)
High Efficiency
Table GD - 4— General Data
6 Ton
7½ Ton
8½ Ton
10 Ton
Convertible Units
Convertible Units
Convertible Units
Convertible Units
THC072A3, A4, AW
THC092A3, A4, AW
THC102A3, A4. AW
THC120A3, A4, AW
Cooling Performance
1
Gross Cooling Capacity
73,000
94,000
103,000
117,000
EER
2
11.5
6
11.5
6
11.5
6
11.2
6
Nominal CFM / ARI Rated CFM
2,400/2,100
3,000/2,625
3,400/3,000
4,000/3,200
ARI Net Cooling Capacity
70,000
90,000
10
98,000
10
109,000
10
Integrated Part Load Value (IPLV)
3
—
11.9
8
12.1
8
12.0
8
System Power (kW)
6.09
7
7.83
7
8.52
7
9.73
7
Compressor
No./Type
1/Climatuff Scroll
2/Climatuff Scrolls
2/Climatuff Scrolls
2/Climatuff Scrolls
Outdoor Sound Rating
(dB)
4
89
91
89
88
Outdoor Coil — Type
Lanced
Lanced
Lanced
Lanced
Tube Size (in.) O.D.
0.3125
0.3125
0.3125
0.3125
Face Area (sq ft)
17.00
17.50
19.83
27.21
Rows/FPI
3/17
3/17
3/17
3/17
Indoor Coil
— Type
Lanced
Lanced
Lanced
Lanced
Tube Size (in.)
0.3125
0.3125
0.3125
0.3125
Face Area (sq ft)
9.89
12.36
12.36
12.36
Rows/FPI
3/16
3/16
4/16
5/16
Refrigerant Control
Short Orifice
Short Orifice
Short Orifice
Short Orifice
Drain Connection No./Size (in.)
1/¾ NPT
1/¾ NPT
1/¾ NPT
1/¾ NPT
Outdoor Fan
— Type
Propeller
Propeller
Propeller
Propeller
No. Used/Diameter (in.)
1/26
1/26
1/26
1/26
Drive Type/No. Speeds
Direct/1
Direct/1
Direct/1
Direct/1
CFM
6100
6200
6600
7000
No. Motors/HP
1/0.70
1/0.70
1/0.75
1/0.75
Motor RPM
1075
1075
1075
1075
Belt Drive Indoor Fan
— Type
FC Centrifugal
FC Centrifugal
FC Centrifugal
FC Centrifugal
No. Used
1
1
1
1
Diameter x Width (in.)
12 x 12
15 x 15
15 x 15
15 x 15
Drive Type/No. Speeds
Belt/Variable Speed
Belt/Variable Speed
Belt/Variable Speed
Belt/Variable Speed
No. Motors
1
1
1
1
Motor HP (Standard/Oversized)
1.00/2.00
2.00/3.00
2.00/3.00
3.00/5.00
Motor RPM (Standard/Oversized)
1750
1750
1750
1750/3450
Motor Frame Size
56
56
56
56
Filters
— Type Furnished
9
Throwaway
Throwaway
Throwaway
Throwaway
(No.) Size Recommended (in.)
(4) 16 x 25 x 2
(4) 20 x 25 x 2
(4) 20 x 25 x 2
(4) 20 x 25 x 2
Optional Hot Gas Reheat Coil
— Type
—
—
—
Lanced
Tube Size (in.) OD
—
—
—
0.375
Face Area (sq. ft.)
—
—
—
5.19
Rows/FPI
—
—
—
2/16
Refrigerant Charge
(Lbs of R-22)
5
10.7
6.4 Circuit 1
7.4 Circuit 1
11.0 Circuit 1
6.2 Circuit 2
7.1Circuit 2
7.3Circuit 2
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment
certification program, which is based on ARI Standard 210/240.
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb ar
ARI rated cfm.
4. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-51.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. EER shown is for downflow airflow. EER for horizontal airflow: THC072A - 11.3, THC092A and THC102A - 11.3, THC120A - 10.7.
7. System Power (kW) shown is for downflow airflow. System Power (kW) for horizontal airflow: THC072A - 6.2, THC092A - 7.88, THC102A - 8.58, THC120A - 10.09.
8. Integrated Part Load Value (IPLV) shown is for downflow airflow. IPLV for horizontal airflow: THC092A - 11.5, THC102A - 11.6, THC120A - 11.5.
9. Optional 2” Pleated Filters also available.
10. Net Cooling Capacity shown is for downflow airflow. Net Cooling for horizontal airflow: THC092A - 89,000, THC102A - 97,000, THC120A - 108,000.