Performance
Water-Cooled
Data
PKG-PRC002-EN
35
Chart PD-29 — SCWF/SIWF 22 Fan Performance for CV or with VFD
22 Ton
Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to
external duct static pressure.
Table PD-7 — SCWF/SIWF 22 Gross Cooling Capacity - 8,800 cfm, 66 gpm
Entering Water Temp
Entering Air
75 F
85 F
95 F
EDB
EWB
Total
Sensible
Total
Sensible
Total
Sensible
F
F
MBh
MBh
LWT
MBh
MBh
LWT
MBh
MBh
LWT
62
257
197
84.3
248
193
94.3
238
188
104.2
75
67
280
159
85.0
270
155
94.9
259
150
104.9
72
305
120
85.8
294
116
95.7
282
112
105.6
62
257
233
84.3
248
228
94.3
238
223
104.2
80
67
280
194
85.0
270
190
94.9
259
186
104.9
72
304
156
85.8
294
152
95.7
282
147
105.6
62
262
261
84.4
254
254
94.4
246
246
104.4
85
67
280
230
85.0
270
226
94.9
259
221
104.8
72
304
191
85.8
293
187
95.7
282
183
105.6
Chart PD-30 — SCWF/SIWF 22 Fan Performance with Inlet Guide Vanes
Содержание CCRC20
Страница 81: ...Dimensions and Weights PKG PRC002 EN 81 Self Contained 20 38 Tons 20 38Ton Self Contained...
Страница 82: ...Dimensions and Weights PKG PRC002 EN 82 40 80Ton Self Contained Self Contained 40 80 Ton 82...
Страница 88: ...Dimensions and Weights PKG PRC002 EN 88 Airside Economizer Airside Economizer...