Performance
Water-Cooled
Data
PKG-PRC002-EN
53
58 Ton
Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used with
these curves, add filter, economizer, flexible horizontal
discharge and heat pressure drops to external duct static
pressure.
Table PD-34. SCWF/SIWF 58 Gross Cooling Capacity - 23,200 cfm, 174 gpm
Entering Water Temp
Entering Air
75 F
85 F
95 F
EDB
EWB
Total
Sensible
Total
Sensible
Total
Sensible
F
F
MBh
MBh
LWT
MBh
MBh
LWT
MBh
MBh
LWT
62
663
571
83.9
637
559
93.8
610
547
103.7
75
67
720
444
84.6
692
433
94.4
662
421
104.3
72
782
316
85.3
751
306
95.2
719
294
105.0
62
675
674
84.1
653
653
94.0
629
629
103.9
80
67
720
564
84.6
692
553
94.4
662
541
104.3
72
781
436
85.3
751
425
95.2
719
414
105.0
62
712
712
84.5
689
689
94.4
665
665
104.3
85
67
725
679
84.6
698
666
94.5
669
652
104.4
72
781
555
85.3
750
545
95.1
718
533
105.0
Chart PD-47. SCWF/SIWF 58 Fan Performance for CV or with VFD
Chart PD-48. SCWF/SIWF 58 Fan Performance with Inlet Guide Vanes