Performance
Water-Cooled
Data
PKG-PRC002-EN
51
52 Ton
Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to
external duct static pressure.
Table PD-31. SCWF/SIWF 52 Gross Cooling Capacity - 20,800 cfm, 156 gpm
Entering Water Temp
Entering Air
75 F
85 F
95 F
EDB
EWB
Total
Sensible
Total
Sensible
Total
Sensible
F
F
MBh
MBh
LWT
MBh
MBh
LWT
MBh
MBh
LWT
62
596
471
84.1
575
461
94.0
551
450
103.9
75
67
650
376
84.8
626
366
94.7
601
356
104.6
72
707
280
85.5
681
271
95.4
654
261
105.3
62
598
559
84.1
577
548
94.0
555
535
104.0
80
67
649
465
84.8
626
455
94.7
600
445
104.6
72
706
369
85.5
680
360
95.4
653
350
105.3
62
616
616
84.3
598
598
94.3
579
579
104.3
85
67
649
554
84.8
625
544
94.7
601
533
104.6
72
705
458
85.5
680
448
95.4
653
438
105.3
Chart PD-45. SCWF/SIWF 52 Fan Performance for CV or with VFD
Chart PD-46. SCWF/SIWF 52 Fan Performance with Inlet Guide Vanes