Performance
Water-Cooled
Data
PKG-PRC002-EN
47
42 Ton
Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to external
duct static pressure.
Table PD-25. SCWF/SIWF 42 Gross Cooling Capacity - 16,800 cfm, 126 gpm
Entering Water Temp
Entering Air
75 F
85 F
95 F
EDB
EWB
Total
Sensible
Total
Sensible
Total
Sensible
F
F
MBh
MBh
LWT
MBh
MBh
LWT
MBh
MBh
LWT
62
488
403
84.1
469
394
94.1
449
385
104.0
75
67
530
317
84.9
510
309
94.7
488
300
104.6
72
576
231
85.6
554
223
95.5
531
215
105.3
62
493
473
84.3
476
460
94.2
458
445
104.1
80
67
530
397
84.9
510
389
94.7
488
380
104.6
72
576
311
85.6
554
303
95.5
530
295
105.3
62
513
512
84.6
496
496
94.5
479
479
104.5
85
67
532
476
84.9
512
467
94.8
491
456
104.6
72
575
391
85.6
553
383
95.5
530
375
105.3
Chart PD-41. SCWF/SIWF 42 Fan Performance for CV or with VFD
Chart PD-42. SCWF/SIWF 42 Fan Performance with Inlet Guide Vanes
Содержание CCRC20
Страница 81: ...Dimensions and Weights PKG PRC002 EN 81 Self Contained 20 38 Tons 20 38Ton Self Contained...
Страница 82: ...Dimensions and Weights PKG PRC002 EN 82 40 80Ton Self Contained Self Contained 40 80 Ton 82...
Страница 88: ...Dimensions and Weights PKG PRC002 EN 88 Airside Economizer Airside Economizer...