Performance
Water-Cooled
Data
PKG-PRC002-EN
49
46 Ton
Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to
external duct static pressure.
Table PD-28. SCWF/SIWF 46 Gross Cooling Capacity - 18,400 cfm, 138 gpm
Entering Water Temp
Entering Air
75 F
85 F
95 F
EDB
EWB
Total
Sensible
Total
Sensible
Total
Sensible
F
F
MBh
MBh
LWT
MBh
MBh
LWT
MBh
MBh
LWT
62
517
449
83.8
498
439
93.6
476
429
103.5
75
67
561
348
84.4
540
340
94.3
516
331
104.1
72
609
248
85.1
586
239
95.0
561
231
104.8
62
530
520
84.0
511
505
93.9
491
488
103.8
80
67
562
444
84.4
539
435
94.3
516
425
104.1
72
609
343
85.1
586
334
95.0
560
325
104.8
62
556
556
84.4
538
538
94.3
518
518
104.2
85
67
567
533
84.5
546
521
94.4
524
505
104.3
72
609
437
85.1
585
428
95.0
559
420
104.5
Chart PD-43. SCWF/SIWF 46 Fan Performance for CV or with VFD
Chart PD-44. SCWF/SIWF 46 Fan Performance with Inlet Guide Vanes