Table PD-1. CFM Capacity Correction Table
Cfm Compared
Cooling
Sensible
To Rated
Capacity
Capacity
Quanitity
Multiplier
Multiplier
-20%
0.970
0.910
-10%
0.985
0.955
DX Cooling
Std
1.000
1.000
+3%
1.005
1.014
+6%
1.009
1.027
-20%
0.970
0.910
-10%
0.985
0.955
Waterside
Std
1.000
1.000
Economizer
+3%
1.005
1.014
+6%
1.009
1.027