background image

Troubleshooting 

• 

Turn off the main power switch immediately if a malfunction is detected. Contact the 
installing dealer or qualified service technician. If the unit continues to run during a 
malfunction, the unit may be damaged or electric shock or fire may occur. 

• 

Do not try to move or reposition the units. Please contact the servicing/installing dealer to 
repair or move the units.  

• 

Check the following items before contacting the dealer or qualified service technician. 

 WARNING

Improper operation may lead to personal injury or casualty. 

Condition

Possible Reason

Unit doesn’t run

When unit is started 
immediately after it is just
turned off

Overload protection switch delays unit start up for 
three minutes 

When power is turned on

The unit is in standby for one minute

Mist comes from the 
unit

When cooling cycle starts

Indoor high humidity air is cooled rapidly

Sound comes from 
the unit

Slight cracking sound is 
heard when unit starts

This sound occurs when the electronic expansion 
valve initializes

There is sound when cooling

The sound of gas refrigerant flowing in unit

There is sound when unit 
starts or stops

This sound occurs when gas refrigerant starts or 
stops flowing

There is slight sound when 
unit is running or after running

The sound of the drainage system operating. 

Cracking sound is heard 
when
unit is operating and after 
operating

This sound occurs when the unit panels expand or 
contract due to temperature change

The unit blows out 
dust

When the unit has been off 
for a period of time. 

Dust in indoor unit is blown out

The unit emits odor When the unit is operating

The room odor absorbed by the unit is blown out 
again

Indoor unit still runs
after switch off

After every indoor unit 
receives the "stop" signal, fan 
will keep running

Indoor fan motor will keep running 20-70 seconds 
to use excess cooling and heating and prepare for 
the next operation

Mode conflict

COOL or HEAT mode can not
be operated

When the indoor operating mode conflicts with 
that of the outdoor unit, the indoor fault indicator 
will flash and conflict will be shown on the wired 
controller after 5 minutes. Indoor unit stops running 
and the outdoor unit changes its mode of operation 
to match the indoor unit, then the unit will go back 
to normal. COOL mode doesn't conflict with DRY 
mode. FAN mode doesn't conflict with any mode

Continuous low 
speed fan operation

Cool or heat mode low speed 
fan operation after setpoint 
temperature achieved

Functionality ensures accurate temperature control 
for the conditioned space

NOTE:

 If the problem persists after checking the above items and taking appropriate measures, 

please stop operation of the unit immediately and contact your local service agency or 
dealer. Diagnostics and repairs should be completed by a professional service technician. 

28

Floor and Ceiling Unit

Содержание 4MXX8509B10N0

Страница 1: ...s Manual Split System R 410A Air Handler for Multi Zone Inverter System 9 000 Btu h to 24 000 Btu h Floor and Ceiling Type Models 4MXX8509B10N0 4MXX8512B10N0 4MXX8518B10N0 4MXX8524B10N0 May 2021 MS S...

Страница 2: ...Attention Warnings and Cautions appear at appropriate sections throughout this literature Read these carefully WARNING Indicates a potentially hazardous situation which if not avoided could result in...

Страница 3: ...trainers must be changed Do not break a vacuum with air Do not leak check the sealed system with compressed air Unless instructed by factory service representative external refrigeration driers are pr...

Страница 4: ...igerant Piping 18 Flaring Processing 18 Bending Pipes 18 Refrigerant Piping at the Outdoor Unit 19 Insulating the Refrigerant Piping and Connections 19 Wiring at the Indoor Unit 20 Stranded Wiring Con...

Страница 5: ...er to the installation specifications for additional requirements 5 Electrical work should be carried out in accordance with the installation manual and local state and National Electric Code NEC Insu...

Страница 6: ...electrical requirements will be met 5 Check the installation locations to ensure the weight of the units can be supported 6 Check the refrigerant pipe sizes and ensure they have been or will be instal...

Страница 7: ...ions may be included in outdoor unit 4 Flare nuts for connecting refrigerant pipes 5 Mounting fasteners 6 Wired remote control and 25 feet of connection cable typically packaged in cellophane bubble N...

Страница 8: ...nit NOTE The minimum distance from the floor to the bottom of the indoor unit is a minimum of 11 75 300mm for floor installation and 90 5 2300mm for ceiling installations Unit Main Components Wireless...

Страница 9: ...xcessive heat from soldering brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids NOTICE System Component Damage Do not remove the seal caps fro...

Страница 10: ...horizontally level 9 Be sure to leave enough space to allow access for routine maintenance clearance between the bottom of the indoor unit and the floor is a minimum of 11 75 300mm for floor installat...

Страница 11: ...rvice Procedures The maintenance and troubleshooting procedures recommended in this section of the manual could result in exposure to electrical mechanical or other potential safety hazards Always ref...

Страница 12: ...bracket by pulling it backward 6 Release the claws in the 3 places indicated 7 Release the center hook and remove the front panel 8 Release the claws in the places indicated on the electric box cover...

Страница 13: ...bolts M6 to prevent displacement of the indoor unit 6 Adjust the height so the rear side of the drain plpe is at a slight decline for improved condensate drainage 7 Reinstall and tighten the right and...

Страница 14: ...ications 2 For ceiling applications the unit must be level side to side Adjust the height of the unit fore and aft to make the drain pipe slant slightly downward so condensate water will flow properly...

Страница 15: ...25mm wall thickness 0 05 inches 1 5mm 6 The drain pipe should be as short as possible and with at least a 0 6 degree slope to avoid forming air pockets Installation of the Condensate Pipe 1 Use the s...

Страница 16: ...forming other installation processes It is recommended to apply a soap bubble solution and observe the connection 5 Evacuate each individual refrigeration circuit to 350 microns or below and close off...

Страница 17: ...will put stress on the indoor unit and could lead to leaking or breakage Install refrigeration lines matching the indoor unit refrigeration tubing diameters Tube adapters are supplied with the outdoo...

Страница 18: ...the flare part is spread evenly and there are no cracks 1 Use a refrigerant pipe bending tool to shape refrigerant piping smaller diameter piping may allow for light hand bending providing minimum di...

Страница 19: ...oor Unit Tighten the flare nut of the connection pipe at the outdoor unit valve connector Follow the flare nut guidelines in this manual Insulating the Refrigerant Piping and Connections 1 The refrige...

Страница 20: ...box of the indoor unit 3 Route the power connection cord from the back of the indoor unit and pull it toward the front through the wiring hole 4 Insert the power cord through the rubber ring 5 Pull th...

Страница 21: ...s Stranded Wire Note Match the terminal block numbers and connection wire colors with those of the indoor units WARNING 1 Ensure power supplied to the equipment both indoor and outdoor units is discon...

Страница 22: ...specification 5 Improperly installed and grounded field wiring poses fire and electrocution hazards For high voltage connections flexible electrical conduit is recommended whenever vibration transmis...

Страница 23: ...nce and must be grounded The yellow green wire of the air conditioner is the ground wire and cannot be used for other purposes or cut off otherwise it would create an electric shock hazard Do not grou...

Страница 24: ...power wiring match the unit requirements Improper wiring can create malfunction and fire or electrocution hazard 9 Are there any obstructions near the air inlets and air outlets for the indoor and ou...

Страница 25: ...Diagram NOTE The wiring diagrams in this guide are included as a reference The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and...

Страница 26: ...mensions 4MXX8509B 4MXX8524B A C Model A B H C D 4MXX8509B 34 2 870 9 2 235 26 2 665 32 812 12 5 318 4MXX8512B 4MXX8518B 4MXX8524B 47 2 1200 9 2 235 26 2 665 45 1142 12 5 318 Unit inch mm 26 Floor and...

Страница 27: ...door ambient temperature sensor is open short circuited F4 Outdoor condenser temperature sensor is open short circuited F5 Outdoor discharge temperature sensor is open short circuited C5 Jumper cap ma...

Страница 28: ...eard when unit is operating and after operating This sound occurs when the unit panels expand or contract due to temperature change The unit blows out dust When the unit has been off for a period of t...

Страница 29: ...water otherwise electric shock may occur Cleaning the Air Filter 1 Open the air inlet grille Open the two buckles on the grille as shown in Fig A below Remove the screws under the buckles with a screw...

Страница 30: ...of the heat exchanger Blow away dust by compressed air if available Never use water to wash the heat exchanger Drain Pipe Regularly check to see if the drain pipe is clogged in order to ensure drain c...

Страница 31: ...nit CONFORMSTO ULSTD 1995 CERTIFIEDTO CSASTD C22 2 N0 236 3097844 About Trane and American Standard Heating and Air Conditioning Trane and American Standard create comfortable energy efficient indoor...

Отзывы: