background image

Post Installation Checklist

 

Check the following points before testing the unit:

NO. 

Item to be checked

Possible problem

1

Have the indoor and outdoor units been 
securely installed?

The units may fall, vibrate or make noise. 

2

Has the refrigerant leak test been 
completed? 

Unresolved leaks may cause insufficient 
cooling or heating. 

3

Have the pipes been properly insulated? 

Lack of insulation may cause condensation 
and water damage. 

4

Is the water condensate drainage 
sufficient?

Lack of proper drainage may cause 
condensation and water damage.

5

Does the voltage of the power supply 
comply with the voltage on the nameplate?

Incorrect power supply can create 
malfunction and fire or electrocution 
hazard. 

6

Is the electric wiring and drain piping 
installed correctly? 

Improper wiring and drainage can create 
a malfunction, fire or electrocution hazard 
and water damage to the unit and property.

7

Is the unit grounded properly?

Improper grounding can cause malfunction 
and fire or electrocution hazard. 

8

Does the power wiring match the unit 
requirements?

Improper wiring can create malfunction and 
fire or electrocution hazard. 

9

Are there any obstructions near the air 
inlets and air outlets for the indoor and 
outdoor units?

Improper ventilation and airflow will cause 
insufficient cooling and heating and 
possible freezing and condensate issues at 
the indoor unit. 

10

Have dust and debris been cleaned and 
removed from the installation site? 

Excessive dust and debris in and around 
the units may cause a malfunction or 
damage to the units.

11

Are the gas valve and liquid valve of the 
connection pipes open completely?

Restricted refrigerant flow may cause 
insufficient cooling or heating. 

Test Operation:

1.  Turn on main power to the units. 
2.  Using the remote control, press the ON/OFF button to start operation. 
3.  Press the MODE button to select and test each option for normal operation. Cycle through all 

functions:  AUTO, COOL, DRY, FAN and HEAT (heat pump models only).  

4.  Note: When conducting this test, be mindful of the modes of operation and the ambient 

temperature ranges specified in this manual.

5.  Instruct the end-product user about basic operating, maintenance and troubleshooting 

functions. 

24

Floor and Ceiling Unit

Содержание 4MXX8509B10N0

Страница 1: ...s Manual Split System R 410A Air Handler for Multi Zone Inverter System 9 000 Btu h to 24 000 Btu h Floor and Ceiling Type Models 4MXX8509B10N0 4MXX8512B10N0 4MXX8518B10N0 4MXX8524B10N0 May 2021 MS S...

Страница 2: ...Attention Warnings and Cautions appear at appropriate sections throughout this literature Read these carefully WARNING Indicates a potentially hazardous situation which if not avoided could result in...

Страница 3: ...trainers must be changed Do not break a vacuum with air Do not leak check the sealed system with compressed air Unless instructed by factory service representative external refrigeration driers are pr...

Страница 4: ...igerant Piping 18 Flaring Processing 18 Bending Pipes 18 Refrigerant Piping at the Outdoor Unit 19 Insulating the Refrigerant Piping and Connections 19 Wiring at the Indoor Unit 20 Stranded Wiring Con...

Страница 5: ...er to the installation specifications for additional requirements 5 Electrical work should be carried out in accordance with the installation manual and local state and National Electric Code NEC Insu...

Страница 6: ...electrical requirements will be met 5 Check the installation locations to ensure the weight of the units can be supported 6 Check the refrigerant pipe sizes and ensure they have been or will be instal...

Страница 7: ...ions may be included in outdoor unit 4 Flare nuts for connecting refrigerant pipes 5 Mounting fasteners 6 Wired remote control and 25 feet of connection cable typically packaged in cellophane bubble N...

Страница 8: ...nit NOTE The minimum distance from the floor to the bottom of the indoor unit is a minimum of 11 75 300mm for floor installation and 90 5 2300mm for ceiling installations Unit Main Components Wireless...

Страница 9: ...xcessive heat from soldering brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids NOTICE System Component Damage Do not remove the seal caps fro...

Страница 10: ...horizontally level 9 Be sure to leave enough space to allow access for routine maintenance clearance between the bottom of the indoor unit and the floor is a minimum of 11 75 300mm for floor installat...

Страница 11: ...rvice Procedures The maintenance and troubleshooting procedures recommended in this section of the manual could result in exposure to electrical mechanical or other potential safety hazards Always ref...

Страница 12: ...bracket by pulling it backward 6 Release the claws in the 3 places indicated 7 Release the center hook and remove the front panel 8 Release the claws in the places indicated on the electric box cover...

Страница 13: ...bolts M6 to prevent displacement of the indoor unit 6 Adjust the height so the rear side of the drain plpe is at a slight decline for improved condensate drainage 7 Reinstall and tighten the right and...

Страница 14: ...ications 2 For ceiling applications the unit must be level side to side Adjust the height of the unit fore and aft to make the drain pipe slant slightly downward so condensate water will flow properly...

Страница 15: ...25mm wall thickness 0 05 inches 1 5mm 6 The drain pipe should be as short as possible and with at least a 0 6 degree slope to avoid forming air pockets Installation of the Condensate Pipe 1 Use the s...

Страница 16: ...forming other installation processes It is recommended to apply a soap bubble solution and observe the connection 5 Evacuate each individual refrigeration circuit to 350 microns or below and close off...

Страница 17: ...will put stress on the indoor unit and could lead to leaking or breakage Install refrigeration lines matching the indoor unit refrigeration tubing diameters Tube adapters are supplied with the outdoo...

Страница 18: ...the flare part is spread evenly and there are no cracks 1 Use a refrigerant pipe bending tool to shape refrigerant piping smaller diameter piping may allow for light hand bending providing minimum di...

Страница 19: ...oor Unit Tighten the flare nut of the connection pipe at the outdoor unit valve connector Follow the flare nut guidelines in this manual Insulating the Refrigerant Piping and Connections 1 The refrige...

Страница 20: ...box of the indoor unit 3 Route the power connection cord from the back of the indoor unit and pull it toward the front through the wiring hole 4 Insert the power cord through the rubber ring 5 Pull th...

Страница 21: ...s Stranded Wire Note Match the terminal block numbers and connection wire colors with those of the indoor units WARNING 1 Ensure power supplied to the equipment both indoor and outdoor units is discon...

Страница 22: ...specification 5 Improperly installed and grounded field wiring poses fire and electrocution hazards For high voltage connections flexible electrical conduit is recommended whenever vibration transmis...

Страница 23: ...nce and must be grounded The yellow green wire of the air conditioner is the ground wire and cannot be used for other purposes or cut off otherwise it would create an electric shock hazard Do not grou...

Страница 24: ...power wiring match the unit requirements Improper wiring can create malfunction and fire or electrocution hazard 9 Are there any obstructions near the air inlets and air outlets for the indoor and ou...

Страница 25: ...Diagram NOTE The wiring diagrams in this guide are included as a reference The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and...

Страница 26: ...mensions 4MXX8509B 4MXX8524B A C Model A B H C D 4MXX8509B 34 2 870 9 2 235 26 2 665 32 812 12 5 318 4MXX8512B 4MXX8518B 4MXX8524B 47 2 1200 9 2 235 26 2 665 45 1142 12 5 318 Unit inch mm 26 Floor and...

Страница 27: ...door ambient temperature sensor is open short circuited F4 Outdoor condenser temperature sensor is open short circuited F5 Outdoor discharge temperature sensor is open short circuited C5 Jumper cap ma...

Страница 28: ...eard when unit is operating and after operating This sound occurs when the unit panels expand or contract due to temperature change The unit blows out dust When the unit has been off for a period of t...

Страница 29: ...water otherwise electric shock may occur Cleaning the Air Filter 1 Open the air inlet grille Open the two buckles on the grille as shown in Fig A below Remove the screws under the buckles with a screw...

Страница 30: ...of the heat exchanger Blow away dust by compressed air if available Never use water to wash the heat exchanger Drain Pipe Regularly check to see if the drain pipe is clogged in order to ensure drain c...

Страница 31: ...nit CONFORMSTO ULSTD 1995 CERTIFIEDTO CSASTD C22 2 N0 236 3097844 About Trane and American Standard Heating and Air Conditioning Trane and American Standard create comfortable energy efficient indoor...

Отзывы: