Installing the Indoor Unit
11
Floor and Ceiling Unit
Mounting Location
1. Confirm the mounting location with the customer. Keep in mind the basic installation
guidelines on page 10.
2. The drilling of holes in the ceiling must be done by the installing technician.
3. Ensure the hanging point is strong enough to support 4 times the weight of the unit.
4. The weight of the unit should be shared equally by the expansion bolts.
>300 mm
>1000 mm
>300 mm
>300 mm
>1500 mm
>300 mm
>300 mm
>300 mm
>1500 mm
>150 mm
>2300 mm
POWER
RUN
TIMER
>11.75 inch
>
11.75 inch
>11.75 inch
>11.75 inch
>59 inch
>39 inch
>6 inch
>11.75 inch
>90 inch
>59 inch
>11.75 inch
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in this section of the
manual could result in exposure to electrical, mechanical or other potential safety
hazards. Always refer to the safety warnings provided throughout this manual
concerning these procedures. Disconnect all electrical power including remote
disconnect and discharge all energy storing devices such as capacitors before
servicing. Follow proper lockout/tag out procedures to ensure the power can not be
inadvertently energized. When necessary to work with live electrical components, have
a qualified licensed electrician or other individual who has been trained in handling live
electrical components perform these tasks. Failure to follow all of the recommended
safety warnings provided, could result in death or serious injury.
Clearance Requirements