20
CVHE-SVX005B-EN
Table 3. Representative weights, 50 Hz chillers (lb) (continued)
Model
Comp Size
CPKW
Evap Size
Cond Size
Weights without Starters
Weights with Starters
NTON
EVSZ
CDSZ
Operating
Shipping
Operating
Shipping
CVHG
480–565
489
050S
050S
22258
19747
22815
20304
480–565
489
050S
050L
23274
20504
23831
21061
480–565
489
050L
050L
24391
21244
24948
21801
480–565
489
050S
080S
25874
22538
26431
23095
480–565
489
050L
080L
28712
24647
29269
25204
480–565
489
080S
080L
33279
28754
33836
29311
670–780
621
080S
080S
32952
28732
33509
29289
670–780
621
080S
080L
34540
30015
35097
30572
670–780
621
080L
080L
36561
31431
37118
31988
670–780
621
080L
142L
45020
38203
45577
38760
670–780
621
142M
142L
49518
41562
50075
42119
670–780
621
142L
142L
50789
42475
51346
43032
920–1100
621
080L
142L
46086
39269
46643
39826
920–1100
892
142M
142L
50988
43032
51545
43589
920–1100
892
142L
142L
52259
43945
52816
44502
920–1100
892
142M
210L
56984
47879
57541
48436
920–1100
892
142L
210L
58205
48792
58762
49349
920–1100
892
142E
210L
59630
49778
60187
50335
920–1100
892
210L
210L
63821
53751
64378
54308
Notes:
1
.
TECU tubes, 0.028 in. tube wall thickness.
2
.
300 psig marine waterboxes.
3
.
Heaviest possible bundle and motor combination.
4
.
Operating weights assume the largest possible refrigerant charge.
5
.
Weights with starters assume the heaviest possible starter (AFD when it’s an allowed option).
6
.
Industrial Control Panel (INDP) option, add 50 lb.
7
.
Control Power Transformer (CPTR) option, add 130 lb.
8
.
Supplemental Motor Protection (SMP) option, add 500 lb.
Weights (kg)
IIm
mp
po
orrtta
an
ntt:: The weight information provided here
should be used for general information
only. Trane does not recommend using this
weight information for considerations
relative to chiller handling, rigging, or
placement. The large number of variances
between chiller selections drives variances
in chiller weights that are not recognized in
these tables. For specific weights for your
chiller, refer to your submittal package.