background image

Open a tap to start up the pump, close it again 

and wait for the pump to stop in order to read 

the system pressure on the pressure gauge, 

which is normally factory-calibrated at 45 psi. 

To adjust the pressure open the tap again, turn 

the knob in a clockwise direction to increase the 

pressure, and in a counterclockwise direction 

to reduce it, close the tap and with the pump 

stopped read the pressure set on the pressure 

gauge.

Repeat this operation until the desired pressure 

value is reached

PRESSURE ADJUSTING PROCEDURE

The system pressure (P2) must be approximately 25 psi lower than the pump pressure (P1), and approximate-

ly 15 psi higher than the pressure in the water column feeding the TOTAL CONTROL (P3).

If the pressure of the pump (P1) fails to reach the values indicated in the pressure adjustment table, the pump 

will stop working. 

In the event of the height of the water column (P3) being higher than the values indicated in the pressure ad-

justment table, the pump will turn on without starting to operate. 

To overcome this shortcoming either positions the device higher up in order to recreate the conditions specified 

above or set a higher system pressure (P2).

Adjusting example:

P1- Pressure pump (maximum 174 psi) 

P2 - System pressure (maximum 95 psi) 

P3 - Water column pressure 

P4 - Tap pressure 

How to deliver a 45 psi pressure to the tap located at a height 

of 90 ft: 

Pressure requested by the service = 45 psi = P4 

Service height 90 ft = 40 psi = P3 

The system pressure (P2) must be adjusted to 85 psi, seeing 

that P2 = P4 + P3. 

The pump pressure (P1) must be a minimum of 110 psi, seeing 

that P1 = P2 + 25 psi.

Содержание PCTC16F16S

Страница 1: ...components Eliminates pump pressure switch Assists in absorbing water hammer Built in pressure and flow switch Can be used with or without pressure tank e m i t d n a e c a p s s e v a s n o i t a l l...

Страница 2: ...ical connections 9 Installation wiring diagram 115 VAC 2 wire pumps up to 16 FLA 9 Installation wiring diagram 230 VAC 2 wire pumps up to 20 FLA 10 Installation wiring diagram 230 VAC 3 wire pumps up...

Страница 3: ...stem and disconnect power supply before installing or servicing TOTAL CONTROL Make sure line voltage and frequency of power supply match motor nameplate voltage and frequency and TOTAL CONTROL voltage...

Страница 4: ...and hold to reset for 3 5 seconds with a tap opened Green Power on light and yellow Pump on should display This indicates system is operating properly If red Failure light comes back on refer to Troub...

Страница 5: ...it without use of liquid tight conduit voids warranty 4 Do not over thighten water connections especially when installing with metal couplings Damage to TOTAL CONTROL may result Prepare all threads wi...

Страница 6: ...INSTALLATION ON SURFACE AND SUBMERSIBLE PUMPS If pressure exceeds 174 psi install a pressure reducing valve SURFACE PUMP TOTAL CONTROL can be installed on surface and submersible pumps for residential...

Страница 7: ...oltage Must always be installed in the vertical position flow arrows up electronic box level Do not install any tap or tee between the pump and the TOTAL CONTROL Install a gate valve after the TOTAL C...

Страница 8: ...m pressure can be adjusted between minimum 45 psi and maximum 95 psi Open a tap to start up the pump close the tap and wait for pump to stop then check the system pressare on the pressure gauge normal...

Страница 9: ...AL CONTROL P3 If the pressure of the pump P1 fails to reach the values indicated in the pressure adjustment table the pump will stop working In the event of the height of the water column P3 being hig...

Страница 10: ...of pump and supply to determine pump motor FLA and follow applicable TOTAL CONTROL wiring diagram If pump motor FLA exceeds TOTAL CONTROL rating use magnetic starter wiring diagram for the applicable...

Страница 11: ...INSTALLATION WIRING DIAGRAM 230VAC 2 WIRE PUMPS UP TO 20 FLA INSTALLATION WIRING DIAGRAM 230VAC 3 WIRE PUMPS UP TO 20 FLA 10...

Страница 12: ...exceed 16 FLA On 230V installations pump motor full load amps exceed 20 FLA On all three phase applications Remember match coil voltage on contactor with TOTAL CONTROL voltage Either 115V or 230V coil...

Страница 13: ...230 VAC THREE PHASE 3 WIRE PUMPS INSTALLATION WIRING DIAGRAM 460VAC For 460Vac motors use magnetic starter to avoid damage to TOTAL CONTROL 12 For 208Vac or 230Vac three phase motors use magnetic sta...

Страница 14: ...OVERALL DIMENSIONS 13 INSTALLATION WIRING DIAGRAM 230VAC 3 WIRE PUMPS EXCEEDING 20 FLA...

Страница 15: ...will not operate WARNING Do not turn on power until the box cover has been securely fastened 4 Install the new electronic box and tighten the three screws Do not overthighten or damage to t hreads may...

Страница 16: ...OTAL CONTROL is warranted to be free of defects occurring either in hydraulic or electronic parts for a period of one year from the date of installation when installed by a licensed professional in ac...

Отзывы: