8. Technical data
8.1. Screen Symbols
See
Section 6.2
and
Section 7.1
for full description.
8.2. Controller
Mains voltages:
Terminal L1 (15), L2/N (14), T2 (13) and T1 (12)
Option:
110 (-15%) … 120 V (+10%) (Voltage fluctuation: 93 … 132 VAC)
Allowable mains supply sys-
- Three-phase four-wire system with earthed neutral
tems and mains voltage:
(symmetrical TN and TT networks)
66/115 V
120/208 V
- Single-phase (split-phase) three-wire systems
110/220 V
115/230 V
120/240 V
Remarks to voltage value above:
- „Outer conductor–neutral conductor“/„Outer conductor–outer con-
ductor“
Standard:
220 (-15%) … 240 V (+10%) (Voltage fluctuation: 187 … 264 VAC)
Allowable mains supply sys-
- Three-phase four-wire system with earthed neutral
tems and mains voltage:
(symmetrical TN and TT networks)
127/220V
220/380 V
230/400 V
240/415 V
- Single-phase (split-phase) three-wire systems
110/220 V
115/230 V
120/240 V
220/440 V
240/480 V
Remarks to voltage value above:
- „Outer conductor–neutral conductor“/„Outer conductor–outer con-
ductor“
Option:
380 (-15%) … 415 V (+10%) (Voltage fluctuation: 323 … 457 VAC)
Allowable mains supply sys-
- Three-phase four-wire system with earthed neutral
tems and mains voltage:
(symmetrical TN and TT networks)
220/380 V
230/400 V
240/415 V
Remarks to voltage value above:
- „Outer conductor–neutral conductor“/„Outer conductor–outer con-
ductor“
Mains connection:
Connection between outer and neutral conductor or between two outer conductors, whereby the nom-
inal voltage between outer conductor and earth must not exceed 300 V.
Overvoltage category:
III
Mains frequency:
50 - 60 Hz
(Frequency fluctuation: 45 … 65 Hz)