PIREG 545 cUL Operators Guide 2021
38
Configuration Menu 218 –
Temp. Diagnosis Time Delay
CONFIGURATION 218
Time delay for
temp.diagnos.: 88.8s
(0.0...99.9s)
Setting of delay for temperature control. Temperature control starts
only after sequence of this delay. Delay starts when true value
reaches temperature-OK-zone.
Configuration Menu 219 –
Heat-Up Time Out
CONFIGURATION 219
Heatup time
out: OFF
(OFF/0.0...99.9s)
Selection for heat-up timeout. At the activation of a “start” signal, the
PIREG
®
545 monitors the time taken to reach the desired “Set” tem-
perature OK-zone. If the “Set” temperature OK-zone is not achieved
within the selected heat-up timeout period, the controller will fault,
and the error code 304 will be displayed. Heat-up timeout can be
programmed OFF or from 0.0 to 99.9 seconds. The OK zone is set
in the Configuration menu 207 and 208.
This is also used to for setting of possible preheating time, during
which actual measured temperature value must be within tempera-
ture OK-zone.
Configuration Menu 222 –
Output 1 Function
CONFIGURATION 222
Output 1 OFF
Selection function of Output 1: For complete list of options refer to
Section 5.10. “Relay and Output Functions”.
Press the Menu Scroll
to advance to Configuration 223 menu. If
the Output 1 function is programmed to generate seal phase impulse
(5) or cooling phase impulse (6), press Menu Scroll
to advance
to Configuration Menu 222a to set duration time of pulse.
Configuration Menu 222a –
Output 1 Impulse Duration
CONFIGURATION 222a
Set duration: 88.8s
(0...99.9s)
:
Setting of the duration of impulse.
Configuration Menu 223 –
Output 1 Switching Mode
CONFIGURATION 223
Output 1: normal
(normal/inverse)
:
Selection for switching mode of output 1 at activated either close
(“normal”) contact or break (“inverse”) contact.
Show selectable setting zone.
Configuration Menu 225 –
Temperature Unit C° or F°
CONFIGURATION 225
Temperature unit:
Celsius
(Celsius/Fahrenheit)
Selection of temperature units