– 3
3
–
Item
2. Indoor fan
motor control
Operation flow and applicable data, etc.
<In heating operation>
Description
1) When setting the fan speed to L,
L+, M, M+ or H on the remote
controller, the operation is per-
formed with the constant speed
shown in Fig. 3 and Table 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 5 according to the set
temperature and room temperature.
3) Min air flow rate is controlled by
temperature of the indoor heat
exchanger (Tc) as shown in Fig. 4
for prevent high temperature of heat
exchanger.
4) Cold draft prevention, the fan speed
is controlled by temperature of the
[In starting and in stability]
(Fig. 3)
(Fig. 4)
(Fig. 5)
Cold draft preventive control
(Fig. 6)
L
L+
M
M+
H
W8
(L + M) / 2
WA
(M + H) / 2
WE
Indication
Fan speed
Fan speed setup
HEAT ON
AUTO
YES
NO
MANUAL
TC
≥
107.6ºF (42 C)
Min air flow rate control
Tc ºF (ºC)
Limited to Min WD tap
* Fan speed =
(TC –
– W8) + W8
No limit
*
Fan speed
AUTO
Basic fan control
* No limitation while fan speed MANUAL mode is in stability.
* A: When Tsc
≥
75°F (24°C), A is 75°F (24°C), and
Tsc: Set value
b
c
d
e
f
g
L+ (W9)
M+ (WD)
*1
*2
*3
H (WE)
H (WE)
Linear-approximate
H and SUL with Tc.
SUL (W2)
Stop
115 (46) 115 (46)
Tc
93 (34)
*A+4
*A+4
*A+4
*A-4
*A-4
*A-4
Fan speed MANUAL in starting
Fan speed AUTO in stability
Fan speed AUTO in starting
*1: Fan speed = [(M+)
− (
L+)] x 1 4 + L+
*2: Fan speed = [(M+)
− (
L+)] x 2 4 + L+
*3: Fan speed = [(M+)
− (
L+)] x 3 4 + L+
(Calculated with linear approximation from M+ and L+)
Ta °F [°C]
TSC
-
1.0
(-0.5)
-
2.0
(-1.0)
-2.7 (-1.5)
-3.
5
(-2.0)
-4.5 (-2.5)
-9.0 (-5.0)
-
10.0
(-5.5)
°F (°C)
113 (45) 113 (45) 91 (33)
91 (33) 91 (33)
70 (21)
90 (32) 90 (32)
68 (20)
when Tsc < 75°F (24°C), A is Tsc
FAN AUTO
FAN Manual
In starting
• Until 12 minutes passed after operation start
• When 12 to 25 minutes passed after operation
start and room temp. is 5.4°F (3°C) or lower than set temp.
• Room temp. < Set temp. -7°F (– 4°C)
In stability
• When 12 to 25 minutes passed after operation start
and room temp. is higher than [set temp. -5.4ºF (–3°C)]
• When 25 minutes or more passed after operation start
• Room temp.
≥
Set temp. -6.3°F (–3.5°C)
5) In order to prevent Cold draft when
compressor stop during heating
operation. Then louver will move to
upper position and fan speed will
reduce or off.
FILE NO. SVM-13069
126 (52)
124 (51)
108 (42)
106 (41)
indoor
h
eat exchanger (Tc) as shown
in Fig. 6 for keep warm
temperature
of air flow.
Содержание RAS-09EAV-UL
Страница 18: ...5 WIRING DIAGRAM 5 1 RAS 09EKV UL RAS 09EAV UL FILE NO SVM 13069 18 ...
Страница 19: ... 19 FILE NO SVM 13069 5 2 RAS 09EKV UL RAS 09EAV2 UL ...
Страница 20: ...5 3 RAS 12EKV UL RAS 12EAV UL FILE NO SVM 13069 20 ...
Страница 21: ...FILE NO SVM 13069 5 4 RAS 12EKV UL RAS 12EAV2 UL 21 ...
Страница 164: ...TOSHIBA CARRIER THAILAND CO LTD ENGINEERING DATA BOOK 1 1 Inverter Single Split RAS 09 22EKV UL RAS 09 22EAV2 UL ...