7-2. Operation Data
<Cooling>
Tempeature
Model name
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
RAS-
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P Psia (MPa)
T1 °F (°C)
T2 °F (°C)
(rps)
80/67 98/75 137 to 160 54 to 57 99 to 102
(26.7/19.4) (35/23.9) (0.9 to 1.1) (12 to 14) (37 to 39)
116 to 145
52 to 55
104 to 107
(0.8 to 1.0)
(11 to 13)
(42 to 44)
<Heating>
Tempeature
Model name
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
RAS-
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P Psia (MPa)
T1 °F (°C)
T2 °F (°C)
(rps)
70/60
47/43
363 to 392
102 to 105
32 to 37
(21.1/15.6)
(8.3/6.1)
(2.5 to 2.7)
(39 to 41)
(0 to 3)
377 to 406
106 to 106
32 to 36
(2.6 to 2.8)
(41 to 43)
(0 to 2)
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 16 ft (5m)
62
High
High
64
09EKV-UL
12EKV-UL
High
High
12EKV-UL High High 77
High High 60
09EKV-UL
FILE NO. SVM-13069
– 2
5
–
Содержание RAS-09EAV-UL
Страница 18: ...5 WIRING DIAGRAM 5 1 RAS 09EKV UL RAS 09EAV UL FILE NO SVM 13069 18 ...
Страница 19: ... 19 FILE NO SVM 13069 5 2 RAS 09EKV UL RAS 09EAV2 UL ...
Страница 20: ...5 3 RAS 12EKV UL RAS 12EAV UL FILE NO SVM 13069 20 ...
Страница 21: ...FILE NO SVM 13069 5 4 RAS 12EKV UL RAS 12EAV2 UL 21 ...
Страница 164: ...TOSHIBA CARRIER THAILAND CO LTD ENGINEERING DATA BOOK 1 1 Inverter Single Split RAS 09 22EKV UL RAS 09 22EAV2 UL ...