– 113 –
6-8-7. Error/Operation Output
Operation
In-operation output: An in-operation indication signal is output as long as at least one indoor unit is in operation in
the line.
Error output: An error indication signal is output if an error occurs in at least one indoor/outdoor unit in the line.
Note 1: Output Relay (K1, K2, K3) Contact Specifications
• Output terminals (OUTPUT1, 2, 3) must satisfy the following electrical rating.
• When connecting a conductive load (e.g. relay coil) to loads K1, K2 and K3, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
The optional P.C. board should be connected to the header outdoor unit (U1).
<Electrical Rating>
220-240 VAC, 10 mA or more, 1A or less
24 VAC, 10 mA or more, 1 A or less (non-conductive load)
C1
Connector cable 1
CN511
Connector on Interface side (green)
K1,K2
Relays
L1
Error indication Lamp
L2
Operation indication Lamp
OUTPUT1
Error output
OUTPUT2
Operation output
PJ20
Connector on optional PCB side
TB1
Terminal block
OUTPUT1
CN511
PJ20
OUTPUT2
OUTPUT3
TB1
L1
L2
1
2
5
6
4
3
C1
PS
PS
K1
K2
1 2 3 4
ON
OFF
SW16
Optional PCB
Locally procured
(See “NOTE”)
Header outdoor unit
Outdoor unit
interface PCB
Shield
wire
Содержание MMY-MAP0804HT7JP
Страница 23: ... 22 1 Wiring Diagrams 1 1 Outdoor Unit Models MMY MAP0804 MAP1004 and MAP1204 ...
Страница 24: ... 23 Models MMY MAP1404 and MAP1604 ...
Страница 35: ... 34 1 2 10 Slim Duct Type AP024 AP027 Models MMD AP0244SPH MMD AP0274SPH ...
Страница 38: ... 37 1 2 13 High Wall Type 3 series Models MMK AP0073H AP0093H AP0123H AP0153H AP0183H AP0243H ...
Страница 52: ... 51 2 5 Parts Layout in Outdoor Unit 8 10 12HP Model MMY MAP0804 MAP1004 MAP1204 ...
Страница 53: ... 52 14 16HP Model MMY MAP1404 MAP1604 ...
Страница 57: ... 56 2 7 2 Inverter P C board for compressor MCC 1596 A3 IPDU ...
Страница 323: ......