7-7-4. Remote Controller Distinction Function
This function is provided to distinguish the remote controller connected to the indoor unit from the outdoor unit for
a refrigerant circuit system by using switches on the interface P.C. board of the header unit.
<Distinction procedure>
Power ON
End
Check the connected remote controller
Operation
7-segment display
[A] [B]
[
A 1
] [
]
7-segment display
[A] [B]
[
A 1
] [
FF
]
Be sure to turn on the power of the indoor unit
prior to the power of the outdoor unit.
Set the display select switches on the
interface P.C. board of the header unit
as follows:
Set SW01/SW02/SW03 to [2/4/1]
Press the push-switch SW04 on the
same board for 2 seconds or more.
"Checking" display of the connected
remote controller flashes.
Press the push-switch SW05 on the
interface P.C. board of the header
unit for 2 seconds or more.
Other end conditions:
1. 10 minutes has passed
2. SW01, SW02, or SW03 changed to other position.
Interface P.C. board
SW04
SW05
SW02
SW03
SW01
7-segment display [A]
7-segment display [B]
<Rotary switches>
Содержание MMY-MAP0804HT7JP
Страница 23: ... 22 1 Wiring Diagrams 1 1 Outdoor Unit Models MMY MAP0804 MAP1004 and MAP1204 ...
Страница 24: ... 23 Models MMY MAP1404 and MAP1604 ...
Страница 35: ... 34 1 2 10 Slim Duct Type AP024 AP027 Models MMD AP0244SPH MMD AP0274SPH ...
Страница 38: ... 37 1 2 13 High Wall Type 3 series Models MMK AP0073H AP0093H AP0123H AP0153H AP0183H AP0243H ...
Страница 52: ... 51 2 5 Parts Layout in Outdoor Unit 8 10 12HP Model MMY MAP0804 MAP1004 MAP1204 ...
Страница 53: ... 52 14 16HP Model MMY MAP1404 MAP1604 ...
Страница 57: ... 56 2 7 2 Inverter P C board for compressor MCC 1596 A3 IPDU ...
Страница 323: ......