– 69 –
5
Fan speed
control
1. The fan operates in one of the four speed modes of “HIGH (HH)”, “MED (H)”,
“LOW (L)” and “AUTO” on the basis of a command issued via the remote
controller. (Concealed duct high static pressure type: HH only)
2. In AUTO fan speed mode, the air speed changes according to the difference
between Ta and Ts.
<Cooling>
HH > H+ > H >
L+ > L > UL
or LL
• Control is identical in remote controller thermo and body thermo operation.
Speed modes shown in < > apply to cooling operation under AUTO air
conditioner operation mode.
• In AUTO fan speed mode, the fan speed remains the same for 3 minutes each
time a speed change occurs.
However, a speed change command issued via the remote controller can
override this, and the fan speed changes accordingly.
• At the beginning of cooling operation, a higher speed (steeper downward
temperature gradient) is chosen.
• As long as the temperature difference remains on a boundary line, the fan speed
stays the same.
<Heating>
Figures inside ( ) applies to remote controller thermo operation.
Figures outside ( ) applies to body thermo operation.
Speed modes shown in < > apply to heating operation under AUTO air
conditioner operation mode.
DN code “32”
“0000”: Body thermo
“0001”: Remote
controller thermo
• In AUTO fan speed mode, the fan speed remains the same for 1 minute each
time a speed change occurs.
However, a speed change command issued via the remote controller can
override this, and the fan speed changes accordingly.
• At the beginning of heating operation, a higher speed (steeper upward
temperature gradient) is chosen.
• As long as the temperature difference remains on a boundary line, the fan speed
stays the same.
• When TC2 60 °C, the fan speed is raised by one step.
TC2: Indoor heat
exchanger sensor
temperature
3. If the air conditioner goes thermo OFF during heating operation, the fan speed
drops down to LL (breeze).
“HEATING
STANDBY
”
displayed
s
k
r
a
m
e
R
e
n
i
l
t
u
o
n
o
i
t
a
c
i
f
i
c
e
p
S
m
e
t
I
.
O
N
-0.5
Tsc
+0.5
+1.0
+1.5
+2.0
+2.5
+3.0
Ta (°C)
HH
H
L
L
L
H+
L+
A
B
C
D
E
F
G
<HH>
<HH>
<HH>
<HH>
<H>
<H>
<L+>
+4.0
+3.0
+2.0
+1.0
Tsh
-1.0
Ta (°C)
(+2.0)
(+1.5)
(+1.0)
(+0.5)
(0)
(-0.5)
L
L+
H
H+
HH
E
D
C
B
A
<L+>
<H>
<H+>
<HH>
<HH>
Содержание MMY-MAP0804HT7JP
Страница 23: ... 22 1 Wiring Diagrams 1 1 Outdoor Unit Models MMY MAP0804 MAP1004 and MAP1204 ...
Страница 24: ... 23 Models MMY MAP1404 and MAP1604 ...
Страница 35: ... 34 1 2 10 Slim Duct Type AP024 AP027 Models MMD AP0244SPH MMD AP0274SPH ...
Страница 38: ... 37 1 2 13 High Wall Type 3 series Models MMK AP0073H AP0093H AP0123H AP0153H AP0183H AP0243H ...
Страница 52: ... 51 2 5 Parts Layout in Outdoor Unit 8 10 12HP Model MMY MAP0804 MAP1004 MAP1204 ...
Страница 53: ... 52 14 16HP Model MMY MAP1404 MAP1604 ...
Страница 57: ... 56 2 7 2 Inverter P C board for compressor MCC 1596 A3 IPDU ...
Страница 323: ......