– 166 –
(Error detected by main remote controller)
(Error detected by central control device)
Note: The same error, e.g. a communication error, may result in the display of different check codes depending on the device that detects it.
Moreover, check codes detected by the main remote controller/central control device do not necessarily have a direct impact on air
conditioner operation.
Check code
Display of receiving unit
Typical fault site
Description of error
Main remote
controller
Outdoor 7-segment display
Indicator light block
Sub-code
Flash
E01 – –
No master remote controller,
faulty remote controller
communication (reception)
Signals cannot be received from indoor unit;
master remote controller has not been set
(including two remote controller control).
E02 – –
Faulty remote controller
communication (transmission)
Signals cannot be transmitted to indoor unit.
E09 – –
Duplicated master remote
controller
Both remote controllers have been set as
master remote controller in two remote
controller control (alarm and shutdown for
header unit and continued operation for
follower unit)
Check code
Display of receiving unit
Typical fault site
Description of error
TCC-LINK central
control
Outdoor 7-segment display
Indicator light block
Sub-code
Flash
C05 – –
No indication (when
main remote controller
also in use)
Faulty central control
communication (transmission)
Central control device is unable to transmit
signal due to duplication of central control
device (AI-NET).
C06 – –
Faulty central control
communication (reception)
Central control device is unable to receive
signal.
s
r
e
t
p
a
d
a
k
r
o
w
t
e
n
e
l
p
i
t
l
u
M
–
–
–
Multiple network adapters are connected to
remote controller communication line (AI-
NET).
–
–
–
2
1
C
Blanket alarm for general-
purpose device control
interface
Device connected to general-purpose device
control interface for TCC-LINK/AI-NET is
faulty.
P30 – –
As per alarm unit (see
above)
Group control follower unit
error
Group follower unit is faulty (unit No. and
above detail [
] displayed on main remote
controller)
Operation Timer Ready
Operation Timer Ready
Содержание MMY-MAP0804HT7JP
Страница 23: ... 22 1 Wiring Diagrams 1 1 Outdoor Unit Models MMY MAP0804 MAP1004 and MAP1204 ...
Страница 24: ... 23 Models MMY MAP1404 and MAP1604 ...
Страница 35: ... 34 1 2 10 Slim Duct Type AP024 AP027 Models MMD AP0244SPH MMD AP0274SPH ...
Страница 38: ... 37 1 2 13 High Wall Type 3 series Models MMK AP0073H AP0093H AP0123H AP0153H AP0183H AP0243H ...
Страница 52: ... 51 2 5 Parts Layout in Outdoor Unit 8 10 12HP Model MMY MAP0804 MAP1004 MAP1204 ...
Страница 53: ... 52 14 16HP Model MMY MAP1404 MAP1604 ...
Страница 57: ... 56 2 7 2 Inverter P C board for compressor MCC 1596 A3 IPDU ...
Страница 323: ......