– 99 –
5d
High-ceiling adjustment
(Air flow selection)
1-way cassette (SH)
2-way cassette
* The high-ceiling installation of model AP007 to AP012 can only be
undertaken when the combined capacity of the indoor units connected is
100% or less than the capacity of the outdoor unit.
Do not proceed with high-ceiling installation if this limit is exceeded.
4-way cassette
Ceiling
0000: Standard
Built-in filter
2-way cassette
0000: Standard filter (factory default)
0001: Super long-life filter
4-way cassette
0000: Standard filter (factory default)
Ceiling
0000: Standard filter (factory default)
Concealed duct standard
0000: Standard filter (factory default)
0001: High-performance filter (65%, 90%)
Static pressure selection Concealed duct standard
0000: Standard (factory default)
0001: High static pressure 1
0003: High static pressure 2
0006: Low static pressure
Slim Duct
0000: Standard (factory default)
0001: High static pressure 1
0003: High static pressure 2
0006: High static pressure 3
60
Timer setting
(wired remote controller)
0000: Available (can be performed)
0001: Unavailable (cannot be
performed)
0000: Available
t
n
e
m
p
i
h
s
t
A
n
o
i
t
p
i
r
c
s
e
D
m
e
t
I
N
D
Value
Type
AP015, AP018
AP024
0000
Standard (factory default)
3.5 m or less
3.8 m or less
0001
High-ceiling (1)
4.0 m or less
4.0 m or less
0003
High-ceiling (3)
4.2 m or less
4.2 m or less
Value
Type
AP007~AP030
AP036~AP056
0000
Standard (factory default)
2.7 m or less
2.7 m or less
0001
High-ceiling (1)
3.2 m or less (*)
3.0 m or less
0003
High-ceiling (3)
3.8 m or less (*)
3.5 m or less
Value
Type
AP009~AP012
AP015~AP018
Air flow at outlet
4 directions
3 directions
2 directions
4 directions
3 directions
2 directions
0000
Standard
(factory default)
2.7 m
2.8 m
3.0 m
2.8 m
3.2 m
3.5 m
0001
High-ceiling (1)
–
–
–
3.2 m
3.5 m
3.8 m
0003
High-ceiling (3)
–
–
–
3.5 m
3.8 m
–
Value
Type
AP024~AP030
AP036~AP056
Air flow at outlet
4 directions
3 directions
2 directions
4 directions
3 directions
2 directions
0000
Standard
(factory default)
3.0 m
3.3 m
3.6 m
3.0 m
3.3 m
3.6 m
0001
High-ceiling (1)
3.3 m
3.5 m
3.8 m
3.3 m
3.5 m
3.8 m
0003
High-ceiling (3)
3.6 m
3.8 m
–
3.6 m
3.8 m
–
6
5
0
P
A
~
5
1
0
P
A
e
p
y
T
e
u
l
a
V
0000
Standard (factory default)
3.5 m or less
s
s
e
l
r
o
m
0
.
4
)
1
(
g
n
il
i
e
c
-
h
g
i
H
1
0
0
0
Содержание MMY-MAP0804HT7JP
Страница 23: ... 22 1 Wiring Diagrams 1 1 Outdoor Unit Models MMY MAP0804 MAP1004 and MAP1204 ...
Страница 24: ... 23 Models MMY MAP1404 and MAP1604 ...
Страница 35: ... 34 1 2 10 Slim Duct Type AP024 AP027 Models MMD AP0244SPH MMD AP0274SPH ...
Страница 38: ... 37 1 2 13 High Wall Type 3 series Models MMK AP0073H AP0093H AP0123H AP0153H AP0183H AP0243H ...
Страница 52: ... 51 2 5 Parts Layout in Outdoor Unit 8 10 12HP Model MMY MAP0804 MAP1004 MAP1204 ...
Страница 53: ... 52 14 16HP Model MMY MAP1404 MAP1604 ...
Страница 57: ... 56 2 7 2 Inverter P C board for compressor MCC 1596 A3 IPDU ...
Страница 323: ......