– 108 –
6-8-1. Power peak-cut Control (Standard)
Operation
An external power peak-cut control signal limits the peak capacity of the outdoor unit.
L1: Power peak-cut control indication lamp
SW1: Power peak-cut control ON switch (ON as long as target power peak-cut control has been reached or
exceeded, normally OFF)*1
SW2: Power peak-cut control OFF switch (OFF as long as target power peak-cut control has not been reached or
exceeded, normally ON)*1
*1 The inputs of SW1 and SW2 can be either pulse (100 msec or wider) or step signals.
Do not turn on SW1 and SW2 simultaneously.
* Be sure to provide a contact for each terminal.
Power peak-cut control settings
Two-core cable support <only available with SMMS-i (4 series)>
SMMS-i models allows ON/OFF power peak-cut control to be implemented using a power peak-cut control ON
input (SW1) alone, provided that the J16 jumper wire on the interface P.C. board of the header outdoor unit has
been removed.
Power peak-cut control P.C.
board
SW1
SW2
L1
Interface P.C. board of header outdoor unit
N
O
1
t
i
B
7
0
W
S
F
F
O
1
t
i
B
7
0
W
S
Power peak-cut control ON
signal received
ON
OFF
ON
0% (forced stop)
60% capacity (upper limit regulated)
Power peak-cut control OFF
signal received
OFF
ON
OFF
100% (normal operation)
100% (normal operation)
PJ17
CN513
SW07
TB1
[ON]
[OFF]
TB2
COM
ON
COM
OFF
Bit 2 OFF
L1
SW1
SW2
SW2
SW1
ON
OFF
1 2 3 4
Connection cable
Locally procured
[OPERATION]
L1: Display lamp suring power peak cut control
Optional PCB
Header outdoor unit
Outdoor unit
interface PCB
Display
relay
Power
supply
Shield
wire
Shield
wire
For SW1 and SW2, be sure to provide no-
voltage contacts for each terminal.
The input signals of SW1 and SW2 may be pulse
input (100 msec or more) or continuous make.
PJ17
TB1
TB2
COM
ON
COM
OFF
CN513
SW07
Bit 2 ON
L1
SW1
ON
OFF
1 2 3 4
[ON]
[OFF]
Connection cable
Locally procured
[OPERATION]
L1: Display lamp suring power peak cut control
Optional PCB
Header outdoor unit
J16 Cut
Shield wire
Shield wire
Outdoor unit
interface PCB
Display
relay
Power
supply
Содержание MMY-MAP0804HT7JP
Страница 23: ... 22 1 Wiring Diagrams 1 1 Outdoor Unit Models MMY MAP0804 MAP1004 and MAP1204 ...
Страница 24: ... 23 Models MMY MAP1404 and MAP1604 ...
Страница 35: ... 34 1 2 10 Slim Duct Type AP024 AP027 Models MMD AP0244SPH MMD AP0274SPH ...
Страница 38: ... 37 1 2 13 High Wall Type 3 series Models MMK AP0073H AP0093H AP0123H AP0153H AP0183H AP0243H ...
Страница 52: ... 51 2 5 Parts Layout in Outdoor Unit 8 10 12HP Model MMY MAP0804 MAP1004 MAP1204 ...
Страница 53: ... 52 14 16HP Model MMY MAP1404 MAP1604 ...
Страница 57: ... 56 2 7 2 Inverter P C board for compressor MCC 1596 A3 IPDU ...
Страница 323: ......