30
(1) Display of System Information (Displayed on Header Outdoor Unit Only)
Display detail
Unused
A
B
System capacity
A [...8]~[48]:8 to 48 HP
B [HP]
No. of outdoor units
A [...1]~[...4]:1 to 4
B [...P]
No. of indoor units connected/
A [...0.]~[48.]:0 to 48 (No. of units connected)
No. of units with cooling thermo ON
B [C...0]~[C48]:0 to 48 (No. of units with cooling thermo ON)
No. of indoor units connected/
A [...0.]~[48.]:0 to 48 (No. of units connected)
No. of units with heating thermo ON
B [H...0]~[H48]:0 to 48 (No. of units with heating thermo ON)
Amount of compressor command
A Value displayed in hexadecimal format
correction
B
—
Release control
A Normal: [r. ...], During release control: [r.1]
B
—
Oil equalization control
Normal: [oiL-0]
During oil equalization control: [oiL-1]
Oil equalization request
A Displayed through LED segment lighting pattern
B
Refrigerant/oil recovery operation
A Oil recovery in cooling: [C1], Normal: [C ...]
B Refrigerant recovery in heating: [H1], Normal: [H ...]
Automatic addressing
A [Ad]
B During automatic addressing: [... FF], Normal: [... ... ...]
Power pick-cut
A [dU]
B Normal: [... ... ...], During 50-90% capacity operation: [_50-_90]
While control is based on BUS line input: [E50-E90]
Optional control (P.C. board input)
Displays optional control status
A
B
Operation mode selection: During priority heating (normal)
h.
∗
.
∗
.
∗
.
∗
Priority cooling
c.
∗
.
∗
.
∗
.
∗
Heating only
H.
∗
.
∗
.
∗
.
∗
Cooling only
C.
∗
.
∗
.
∗
.
∗
Priority given to No. of indoor units in operation
n.
∗
.
∗
.
∗
.
∗
Priority given to specific indoor unit
U.
∗
.
∗
.
∗
.
∗
External master ON/OFF: Normal
∗
.....
∗
.
∗
.
∗
Start input
∗
.1.
∗
.
∗
.
∗
Stop input
∗
.0.
∗
.
∗
.
∗
Night operation: Normal
∗
.
∗
.
....
∗
.
∗
.
Start input
∗
.
∗
.
1.
∗
.
∗
.
Snowfall operation: Normal
∗
.
∗
.
∗
.....
∗
.
Start input
∗
.
∗
.
∗
.1.
∗
.
Optional control (BUS line input)
Same as above
Unused
A
—
B
—
SW01 SW02 SW03
1
2
3
4
5
6
7
8
9
1
10
3
11
12
13
14
15
16
If element F shown on sketch at right turned on:
Header unit oil equalization request If element C
shown on sketch at right turned on:
Follower unit oil equalization request
F
G
A
D
U2
U1
U3
U4
Dp
B
E
C
Display section A
Display section B
Outdoor unit No.
Indoor Unit from Outdoor Unit