(5) Display of Indoor Unit Information (Displayed on Header Unit Only)
Display detail
Indoor BUS communication B Upon receiving signal: [... ... 1], Other times: [... ... ...]
signal receiving status
Indoor check code
B No check code: [– – –]
Indoor HP capacity
B 0. 2, 0. 5, 0. 8, ... 1, 1. 2, 1. 7, ... 2, 2. 5, ...3, 3. 2, ...4, ...5, ...6, ...8, 1 0, 1 6, 2 0
Indoor request command
B [ #. ...
∗
]
(S code, operation mode)
# represents mode:
COOL: [C. ...
∗
], HEAT: [H. ...
∗
]
FAN: [F. ...
∗
], OFF: [S. ...
∗
]
∗
represents S code: [#. ... 0] to [#. ... F]
Indoor PMV opening data
B Displayed in decimal format
Indoor TA sensor data
B Displayed in decimal format
Indoor TCJ sensor data
B Displayed in decimal format
Indoor TC1 sensor data
B Displayed in decimal format
Indoor TC2 sensor data
B Displayed in decimal format
Note:
Indoor address No. is selected by setting SW02 and SW03 and displayed on 7-segment display, section A.
Indoor address
SW02 setting number
SW02 setting 16
SW02 setting 32
SW02 setting 48
7-segment display section A
[01]~[16]
[17]~[32]
[33]~[48]
[49]~[64]
∗
Although 64 indoor unit addresses (Nos. 01-64) are theoretically available, the number of indoor units that can be
connected to the same refrigerant piping system is limited to 48.
(6) Display of Outdoor EEPROM Writing Error Code (Displayed on Header Unit Only)
∗
The latest error code written in the EEPROM of each outdoor unit is displayed.
(This function is used to check the error code after the resetting of the power supply.)
To display the error code, push
SW04
and hold for at least 5 seconds after setting
SW01
to 03 as shown in the table
below.
Indoor address
Latest error code of header unit (U1)
Latest error code of follower unit No. 1 (U2)
Latest error code of follower unit No. 2 (U3)
Latest error code of follower unit No. 3 (U4)
7-segment display section A
E. 1.
∗∗∗
E. 2.
∗∗∗
E. 3.
∗∗∗
E. 4.
∗∗∗
• 7-Segment Display
Set SW01/SW02/SW03 to [1/1/16] and push SW04 and hold for at least 5 seconds. The latest error code of the
header unit (U1) will be displayed.
If the setting of SW02 is changed, the latest error code of a follow unit (U2-U4) will be displayed.
Section A
Section B
D600 D601
D602 D603 D604
Indoor Unit from Outdoor Unit (continue)
SW01 SW02 SW03
4
5
6
1~4
7
1~16
8
9
11
12
1~4
13
33
SW03
1
2
3
4
SW02
1~16
1~16
1~16
1~16
SW01 SW02 SW03
1
1
2
16
3
4