Display detail
Error data
A Outdoor unit No.: [U1] to [U4]
B Check code (only latest one displayed)
If there is no check code, [– – –] is displayed.
If there is sub-code, check code [
∗
∗
∗
] and sub-code [-
∗
∗
] are displayed
alternately, for 3 seconds and 1 second, respectively.
<SW04> push SW function: Fan operation at outdoor unit with error. 7-segment display section A: [E.1]
<SW04 + SW05> push SW function: Fan operation at outdoor unit without error. 7-segment display section A: [E.0]
<SW05> push SW function: Fan operation function check mode is cancelled.
—
A
—
B
—
Operation mode
A Stop [... ...]
Normal cooling: [... C], Normal heating: [... H], Normal defrosting: [... J]
B
—
Outdoor unit HP capacity
A 8HP: [... 8], 10HP: [... 10], 12HP: [... 12], 14HP: [14], 16HP: [16]
B [... HP]
Compressor operation command
∗
Operation data of each compressor is displayed in turn in 2 second intervals.
If compressor No. 3 does not exist, [--.---] is displayed.
Normal: Compressor speed (rps) is displayed in decimal format.
7-segment display (A/B): [C1.
∗
∗
∗
]
Ö
[C2.
∗
∗
∗
]
Ö
[C3.
∗
∗
∗
]
Ö
...
<SW04> push SW function: Switches to display of operating current (decimal value).
7-segment display (A/B): [i1
∗
∗
∗
]
Ö
[i2
∗
∗
∗
]
Ö
[i3
∗
∗
∗
] Þ ...
Pushing of <SW05> restores normal display.
Outdoor fan mode
A [FP]
B Mode 0 to 63: [... 0] to [63]
Compressor backup
A [C.b.]
B Displays compressor backup setting status
Normal: [... ... ...]
Compressor No. 1 backup: [1 ... ...]
Compressor No. 2 backup: [... 1 ...]
Compressor No. 3 backup: [... ... 1]
—
A
—
B
—
Control valve output data
Displays control output status of solenoid valve
A
B
4-way valve: ON / 4-way valve 2: OFF
H. 1
... ... ...
4-way valve: OFF / 4-way valve 2: ON
H. 0
... ... ...
SV2: ON / SV5: OFF / SV6: OFF
2. ...
1 0 0
SV2: OFF / SV5: ON / SV6: ON
2. ...
0 1 0
SV2: OFF / SV5: OFF / SV6: ON
2. ...
0 0 1
SV3A: ON / SV3B: OFF / SV3C: OFF / SV3D: OFF
3. 1
0 0 0
SV3A: OFF / SV3B: ON / SV3C: OFF / SV3D: OFF
3. 0
1 0 0
SV3A: OFF / SV3B: OFF / SV3C: ON / SV3D: OFF
3. 0
0 1 0
SV3A: OFF / SV3B: OFF / SV3C: OFF / SV3D: ON
3. 0
0 0 1
SV41: ON / SV42: OFF / SV43: OFF
4. ...
1 0 0
SV41: OFF / SV42: ON / SV43: OFF
4. ...
0 1 0
SV41: OFF / SV42: OFF / SV43: ON
4. ...
0 0 1
SV3F: OFF
A. ...
... ... 0
SV3F: ON
A. ...
... ... 1
PMV1/PMV2 opening
Displays opening data in decimal format (total opening)
∗
∗
∗
∗
.P
PMV4 opening
Displays opening data in decimal format
...
∗
∗
∗
.P
Oil level judgment status
Normal
A [o L.]
B Initial display: [... ... ...], Oil level judgment result: [#.
∗
.$]
Displayed letters #,
∗
and $ represent judgment results for compressor Nos.
1, 2 and 3, respectively (“0” for normal and “1” or “2” for low level).
<SW04> push SW function: Displays low level confirmed judgment result of each compressor.
∗
Pushing of <SW05>
A [L d.]
restores normal display.
B Compressor No. 1 low level being confirmed: [L ... ...]
Compressor No. 2 low level being confirmed: [... L ...]
Compressor No. 3 low level being confirmed: [... ... L]
(2) Display of Outdoor Unit Information (Displayed on Each Outdoor Unit)
Indoor Unit from Outdoor Unit (continue)
31
SW01 SW02 SW03
1
2
3
4
5
6
7
8
1
1
9
10
11
12
13
14
15
16