Check after Address Setup when Central Control System Is Connected
When the central control system is connected, check that the following setup has finished after address setup.
NOTE
The figure above does not show all the electric wires.
For details, refer to the installation manuals for the outdoor unit, indoor unit, remote controller, or optional devices.
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
U5 U6
U3 U4
Header
unit (A)
Header
unit (A)
U1 U2
U5 U6
U3 U4
U1 U2
U5 U6
A B
A B
A B
A B
(5)
(4)
(5)
(1)
(2)
(3)
Other
refrigerant line
U1 U2
U3 U4
U3 U4
U1 U2
U5 U6
To other
refrigerant line
U3 U4
Line address = 2
Line address = 1
%
entral remote
controller
Follower
unit (C)
Follower
unit (B)
Outdoor unit
Indoor unit
Remote controller Remote controller Remote controller
Relay
connector
Terminal
resistance
Line address
Main check items
(1) Is the relay connector of the header unit connected after address setup?
(2) Is the relay connector of the follower unit removed?
(3) Is the end resistance (SW30-bit 2) of the header unit with the smallest line address
number in the central control turned on? (Setup is unnecessary for follower units.)
(4) Is the terminal resistance (SW30-bit 2) of the header units, except for the line with the
smallest central control line address, turned off? (Setup is unnecessary for follower units.)
(5) Are addresses in the line address (SW13, SW14) not duplicated in each refrigerant line?
Check