Function CODE No. (DN Code) Table (Includes All Functions Needed to Perform Applied Control on Site)
DN
01
02
03
04
06
0d
0F
10
11
12
13
14
19
1E
28
2A
31
32
33
F0
F1
F2
F3
F4
Item
Filter display delay timer
Dirty state of filter
Central control address
Specific indoor unit priority
Heating temp shift
Existence of [AUTO] mode
Cooling only
Type
Indoor unit capacity
Line address
Indoor unit address
Group address
Louver type
(Air direction adjustment)
Temp difference of [AUTO] mode selection
COOL
→
HEAT, HEAT
→
COOL
Automatic restart of power failure
Selection of option/error input
(CN70)
Ventilating fan control
TA sensor selection
Temperature unit select
Swing mode
Louver fixed position (Louver No.1)
Louver fixed position (Louver No.2)
Louver fixed position (Louver No.3)
Louver fixed position (Louver No.4)
Description
0000: None
0001: 150H
0002: 2500H
0003: 5000H
0004: 10000H
0000: Standard
0001: High degree of dirt (Half of standard time)
0001: No.1 unit
to
0064: No.64 unit
0099: Unfixed
0000: No priority
0001: Priority
0000: No shift
0001: +1°C
0002: +2°C
to
0010: +10°C (Up to +6 recommended)
0000: Provided
0001: Not provided (Automatic selection from connected outdoor unit)
0000: Heat pump
0001: Cooling only (No display of [AUTO] [HEAT])
0001: 4-way Air Discharge Cassette
0000: Unfixed
0001 to 0034
0001: No.1 unit
to
0030: No.30 unit
0001: No.1 unit
to
0064: No.64 unit
0000: Individual
0001: Header unit of group
0002: Follower unit of group
0000: No louver
0001: Swing only
0002: (1-way Air Discharge Cassette type, Under Ceiling type)
0003: (2-way Air Discharge Cassette type)
0004: (4-way Air Discharge Cassette type)
0000: 0 deg
to
0010: 10 deg
(For setup temperature, reversal of COOL/HEAT by ± (Data value) /2)
0000: None
0001: Restart
0000: Filter input
0001: Alarm input (Air washer, etc.)
0002: None
0000: Unavailable
0001: Available
0000: Body TA sensor
0001: Remote controller sensor
0000: °C (at factory shipment)
0001:°F
0001: Standard
0002: Dual swing
0003: Cycle swing
0000: Release
0001: Horizontal discharge position
0005: Downward discharge position
0000: Release
0001: Horizontal discharge position
0005: Downward discharge position
0000: Release
0001: Horizontal discharge position
0005: Downward discharge position
0000: Release
0001: Horizontal discharge position
0005: Downward discharge position
At shipment
According to type
0000: Standard
0099: Unfixed
0000: No priority
0002: +2°C
(Floor type 0000: 0°C)
0001: Not provided
0000: Heat pump
Depending on model type
According to capacity type
0099: Unfixed
0099: Unfixed
0099: Unfixed
According to type
0003: 3 deg (Ts±1.5)
0000: None
0002: None
0000: Unavailable
0000: Body TA sensor
0000: °C
0001: Standard
0000: Not fixed
0000: Not fixed
0000: Not fixed
0000: Not fixed