Ye
s
Ye
s
Ye
s
Ye
s
No
No
No
Ye
s
No
No
[E18]
Check code
Check code name
Cause
Communication trouble between
indoor header and follower
Regular communication between indoor header and
follower is unavailable.
Are remote
controller inter-unit wires
(A/B) normal?
Is connector
or wiring from
terminal block of indoor
unit connected
correctly?
Is group
control operation
executed?
Are powers of all indoor
units turned on?
Is indoor unit
address correct?
Correct remote controller
inter-unit wire.
Correct connection of
connector
.
Check circuit wire.
Check power connection
status of indoor unit. (T
urn
on the power again.)
Correct indoor unit address.
Replace indoor interface
P.C. board.
Ye
s
No
Ye
s
No
[F01]
Ye
s
No
Ye
s
No
[F02]
Check code
Check code name
Cause
Check code
Check code name
Cause
Indoor TCJ
sensor
trouble
TCJ sensor Open/Short-circuit
Indoor
TC2 sensor trouble
TC2 sensor Open/Short-circuit
Is TCJ
sensor connector
(CN102: Red) on indoor
P
.C. board normally
connected?
Are characteristics
of TCJ
sensor
resistance
value normal?
Is TC2
sensor connector
(CN101: Black) on indoor
P
.C. board normally
connected?
Are characteristics of
TC2 sensor resistance
value normal?
Correct connection of
connector
.
Replace TCJ
sensor
.
Correct connection of
connector
.
Replace TC2
sensor
.
Replace indoor P
.C. board.
Replace indoor P
.C. board.
*See “Indoorunittemperature sensor
characteristics” on
“9-6.
Sensor
Characteristics”.
*See “Indoor unit
temperature sensor
characteristics” on
“9-6.
Sensor
Characteristics”.
- 85 -