No.
8
Item
Freeze prevention
control (Low temp.
release)
Outline of specifications
1. In all cooling operation, the air conditioner operates
as described below based upon temp. detected by
TC1, TC2 and TCJ sensors.
• When “J” zone is detected for 5 minutes, the
thermostat is forcedly off.
• In “K” zone, the timer count is interrupted, and held.
• When “
I
” zone is detected, the timer is cleared
and the operation returns to the normal operation.
• If “J” zone continues, operation of the indoor fan in
LOW mode continues until it reaches the “
I
” zone.
It is reset when the following conditions are satisfied.
Remarks
TC1: Temperature of indoor
heat exchanger sensor
2. In all cooling operation, the air conditioner operates
as described below based upon temp. detected by
TC2 and TCJ sensors.
• When “M” zone is detected for 45 minutes, the
thermostat is forcedly off.
• In “N” zone, the timer count is interrupted and held.
• When shifting to “M” zone again, the timer count
restarts and continues.
• If “L ” zone is detected, the timer is cleared and the
operation returns to normal operation.
( ) value:
When the power supply is
turned on, the forced
thermostat becomes OFF if
the temperature is less than
this indicated temperature.
1.
In heating operation, the higher temperature of TC2
sensor
and TCJ sensor is compared with temperature
of TC1 sensor
and then the lower temperature is
used
to
set the upper limit of the fan tap.
• When B zone has continued for 6 minutes, the
operation
shifts to C zone.
• In defrost time, the control point is
set to
+10.8 ˚F
[+6˚C]
.
TCJ: Temperature of indoor
heat exchanger sensor
• In D and E zones, priority
is given to remote control-
ler fan speed setup.
• In A zone “
” is displayed.
7
Prevention of cold
air discharge
E
B
A
A zone: OFF
B zone:
Over
78.8°F(
26°C
)
, below
82.4°F(
28°C
)
, ULTRA LOW (LL)
C zone:
Over
82.4°F(
28°C
)
, below
86°F(
30°C
)
, LOW (L)
D zone:
Over
86°F(
30°C
)
, below
89.6°F(
32°C
)
, MED (H)
E zone: HIGH (HH)
D
C
32
30
28
26
20
16
(°C)
89.6
86
82.4
78.8
68
33.8
(°
F
)
Reset conditions
1)
TC1
Ӎ
53.6°F(
12°C
)
and TC2
Ӎ
53.6°F(
12°C
)
and
TCJ
Ӎ
53.6°F(
12°C
)
2)
20 minutes passed after stop.
P1
Q1
(°C)
a
K
J
P1
Q1
TC1
32
°
F
(
0
°C)
TC2, TCJ
14
°
F(-10°C)
6.8°F(-14°C)
(°
F
)
50
°
F
(
10
°C)
(41°F)(5°C)
Reset conditions
P2
Q2
L
N
M
P2
Q2
TC2, TCJ
41°F(
5°C
)
28.4
°
F(–2.0°C)
1)
TC1
Ӎ
53.6°F(
12°C
)
and TC2
Ӎ
53.6°F(
12°C
)
and
TCJ
Ӎ
53.6°F(
12°C
)
2)
20 minutes passed after stop.
(°
F
)
(°C)
- 21 -