The sensor temperature or operational status of
indoor unit, outdoor unit, or remote controller can be
monitored.
Monitor function
Code
00
Data
0024
Return
*
Display and the contents
- - - - : Sensor function is not available.
0000 : Normal
0001 : Sensor has been used for 5 years.
0002 : Sensor trouble or exceeding the life of the
product for sensor
000
3
: Sensor is detecting refrigerant leak
Indoor unit data
Code
Data name
01
Room temperature (remote controller)
02
Indoor unit intake air temperature (TA)
0
3
Indoor unit heat exchanger (coil)
temperature (TCJ)
04
Indoor unit heat exchanger (coil)
temperature (TC)
F
3
Indoor unit fan cumulative operating hours
(x1 h)
E2
Indoor unit refrigerant leak detection sensor
output
*
Outdoor unit data
Code
Data name
60
Outdoor unit heat exchanger (coil)
temperature (TE)
61
Outside air temperature (TO)
62
Compressor discharge temperature (TD)
6
3
Compressor suction temperature (TS)
65
Heatsink temperature (THS)
6A
Operating current (x1/10)
6D
Outdoor heat exchange (coil)
temperature (TL)
F1
Compressor cumulative operating hours
(x100 h)
Procedure
1
Push the [
MENU] button to display
the menu screen.
2
Push and hold the [
MENU] button
and the [
] button at the same time
to display the “Field setting menu”.
→
Push and hold the buttons for more than 4
seconds.
3
Push the [
] / [
] button to
select “4. Monitor function” on the “Field
setting menu” screen, then push the “
S
et
Set” [
F2
F2] button.
→
] button to
Push the [
] / [
select the code to check data.
4
Push the [
CANCEL] button to return
to the “Field setting menu” screen.
<RBC-AMS5*E-UL>
- 53 -