Check code
Display of receiving unit
Typical trouble on site
Description of check code
TCC-LINK
central control
or main remote
control
display
Outdoor 7-segment display
Indicator light block
Sub-code
Flash
E03
Indoor-remote control periodic
communication
trouble
Communication from remote control or network adaptor has
been lost (so has central control communication).
E04
Indoor-outdoor periodic
communication
trouble
Signals are not being received from outdoor unit.
E08
E08 Duplicated indoor address
E10
Duplicated indoor address
UART communication
trouble
Indoor unit detects address identical to its own.
Communication
trouble
between CDB(MCC-1643)
and FAN-IPDU(MCC-1610).
E18
Check cod
e
in periodic
communication between indoor
header and follower unit
Periodic communication between indoor header and follower units
cannot be maintained.
F01
ALT
Indoor heat exchanger
temperature sensor (TCJ)
trouble
Heat exchanger temperature sensor (TCJ) has been open /
shortcircuited.
F02
ALT
Indoor heat exchanger
temperature sensor (TC2)
trouble
Heat exchanger temperature sensor (TC2) has been open /
shortcircuited.
F03
ALT
Indoor heat exchanger
temperature sensor (TC1)
trouble
Heat exchanger temperature sensor (TC1) has been open /
shortcircuited.
F10
ALT
Ambient temperature sensor (TA)
trouble
Ambient temperature sensor (TA) has been open / short-circuited.
F11
ALT
Discharge temperature sensor
(TF)
trouble
Discharge temperature sensor (TF) has been open /
shortcircuited.
F29
SIM
Indoor EEPROM is abnormal (some other
trouble
may be
detected).
L03
SIM
Duplicated indoor group header
unit
There is more than one header unit in group.
L07
SIM
Connection of group control cable
to stand-alone indoor unit
There is at least one stand-alone indoor unit to which group control
cable is connected.
L08
L08
SIM
Indoor group address not set
Address setting has not been performed for one or more indoor
units (also detected at outdoor unit end).
L09
SIM Indoor capacity not set
Capacity setting has not been performed for indoor unit.
L20
SIM
SIM
Duplicated central control address There is duplication in central control address setting.
L30
L30
Detected indoor unit No.
Indoor external
trouble
input
(interlock)
Unit shutdown has been caused by external
trouble
input (CN80).
P01
ALT
Indoor AC fan
trouble
Indoor AC fan
trouble
is detected (activation of fan motor
thermal
relay).
P10
P10
Detected indoor unit No.
ALT
Indoor overflow
trouble
Float switch has been activated.
P12
ALT
Indoor DC fan
trouble
(e.g. overcurrent or lock-up) is
detected.
P31
ALT
Other indoor unit
trouble
Follower unit cannot be operated due to header unit alarm
(E03 /L03 / L07 / L08).
IPDU: Intelligent Power Drive Unit (Inverter P.C. board)
: Goes off
: Lighting, : Flashing,
ALT.: Flashing is alternately when there are two flashing LED
SIM: Simultaneous flashing when there are two flashing LED
Timer Ready
Operation
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
Indoor DC fan
trouble
9-2. Troubleshooting method
The remote control
s
(main remote control and central control remote control) and the interface P.C.
board of
an outdoor unit are provided with an LCD display (remote control) or a 7-segment display (outdoor
interface
P.C. board) to display operational status. Using this self-diagnosis feature, the
trouble
site /
trouble
part
may
be identified in the event of a
trouble
by following the method described below.
The list below summarizes check codes detected by various devices. Analyze the check code according to
where it is displayed and work out the nature of the
trouble
in consultation with the list.
• When investigating a
trouble
on the basis of a display provided on the indoor remote control or TCC-LINK
central control remote control -
See the “TCC-LINK remote control or main remote control display” section of the list.
• When investigating a
trouble
on the basis of a display provided on an outdoor unit - See the “Outdoor 7-
segment display” section of the list.
• When investigating a
trouble
on the basis of a wireless remote control-controlled indoor unit - See the
"Indicator light block"
section of the list.
List of check codes (indoor unit)
(Check code
detected by indoor unit)
Communication
trouble
between
Application control
P.C.Board
and indoor unit
Communica
tion check code b
etween Application control
P.C.Board
and indoor unit P.C.
B
oard
E1
1
⎯
⎯
P.C.
B
oard or other indoor
trouble
- 49 -