1. SPECIFICATIONS
Concealed Duct High Static Pressure Type
Model name
MMD-
AP0726HP-UL
AP0966HP-UL
Cooling capacity …Note 1
(kBtu/h)
72.0
96.0
Heating capacity …Note 1
(kBtu/h)
81.0
108.0
Electrical
Power supply
1phase 60Hz 230V (208/230V)
characteristics
Running current (208V / 230V)
(A)
3.10
/
2.80
4.15
/
3.75
(factory setting)
Power consumption
(W)
540
/
540
790
/
790
Starting current
(A)
8.63
/
7.80
8.63
/
7.80
Appearance
Zinc hot dipping steel plate
Dimension
Height
(inch)
17.6
Unit
Width
(inch)
55.1
Depth
(inch)
35.4
Height
(inch)
21.2
Packing
Width
(inch)
69.2
Depth
(inch)
40.8
Total weight
Unit
(lbs)
218
Packed unit
(lbs)
265
Heat exchanger
Finned tube
Soundproof / Heat-insulating meterial
Polyethlene foam
Fan unit
Fan
Centrifugal fan
2,236
2,825
Standard air flow
(Med./Low)
(1883
/
1471)
(2471
/
2059)
Motor output
(
k
W)
1kW * 1pc
External static pressure (factory setting)
(In WG)
0.603
External static pressure range
(In WG)
0.201-0.334-0.470-<0.603>-0.735-0.872-1.005 (7steps)
Cont
rol
Remote control
Connecting
Gas side
(inch)
7/8"
pipe
Liquid side
(inch)
1/2"
Drain port
(inch)
VP25(Polyvinyl chloride tube: External Dia. 1-1/4 Internal Dia.1)
(dB(A))
44 / 40 / 36
46 / 42 / 38
Sound power level (High/Med./Low)
(dB(A))
79 / 75 / 71
81 / 77 / 73
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based
on the reference piping.
The reference piping consists of 5m of main piping and 2.5m of branch piping connected with 0 meter height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616
Normally, the values measured in the actual operating environment become larger than the indicated valves due to the
effects of external sound.
Note
:
Rated conditions Cooling: Indoor air temperature 80
℉
DB/67
℉
WB, Outdoor air temperature 95
℉
DB
Heating: Indoor
air temperature70
℉
DB, Outdoor air temperature47
℉
DB/43
℉
WB
Sound pressure level
(High/Med./Low) …Note 2
(factory setting)
(cfm)