NO.
Item
Specification outline
Remarks
6
7
Cold air
discharge
prevention
control
1.
In heating operation, the upper limit of the fan tap is set according to the
lower of whichever is the higher between TC2 sensor and TCJ sensor
temperatures, on the one hand, and TC1 sensor temperature, on the
other.
• If the fan continuously operates in zone B for 6 minutes, it automatically
moves into zone C.
• During defrosting, the control point is shifted by
+10.8°F[6°C].
TCJ: Indoor heat
exchanger
sensor
temperature
•
•
In zones D and E,
priority is given
to the remote
control fan
speed setting.
In zone A,
“HEATING
STANDBY ”
is displayed.
Freeze
prevention
control (low
temp. release)
1. During cooling, the air conditioner is operated in the manner described
below according to the temperature readings of the TC1, TC2 and TCJ
sensors.
• If zone J operation is detected for 5 minutes, the air conditioner is forced
into th
ermostat
OFF.
• In zone K, the timer is put on pause, with the current timer count
retained.
• If zone I operation is detected, the timer count is cleared, and the air
conditioner returns to normal operation.
• If continuous zone J operation forces the air conditioner into thermo
stat
OFF,
the indoor fan is operated in breeze mode until it moves into zone I.
The control is terminated under the following conditions:
Termination conditions
1) TC1
≥
54°F
(
12
°C
)
, TC2
≥
54°F
(
12°C
)
, and TCJ
≥
54°F
(
12°C
)
TC1:
Indoor heat
exchanger
sensor
temperature
B
A
A zone: OFF
B zone:
7
9
°F(
26˚C
)
or above and
below
82°F(
28˚C
)
breeze
C zone:
82°F(28˚C)
or above and
below
86°F(30˚C)
Low
D zone:
86°F(30˚C)
or above and
below
90°F(32˚C)
Medium
E zone: High
90 (32)
D
86 (30)
C
E
82 (28)
75 (26)
68 (20)
6
1
(16)
°F(°C)
* With models
without TC2,
TC2 is not
part of the
control
parameters.
P1
Q1
°F(°C)
a
K
J
P1
Q1
TC1
50˚F
(10
˚C
)
32˚F
(
0˚C
)
TC2, TCJ
14˚F
(
–10˚C
)
7˚F
(
14˚C
)
I
2) Passage of 20 minutes after stoppage
2. During cooling, the air conditioner is operated in the manner described
below according to the temperature readings of the TC2 and TCJ sensors.
• If zone M operation is detected for 45 minutes, the air conditioner is
forced into thermo OFF.
• In zone N, the timer is put on pause, with the current timer count
retained.
• When the air conditioner goes back into zone M, timer count is resumed
from the retained value.
°F(°C)
P2
Q2
L
N
M
P2
Q2
TC2, TCJ
41°F
(
5°C
)
28
°F
(
2°C
)
• If zone L operation is detected, the timer count is cleared, and the air
conditioner returns to normal operation.
Reset conditions
1)
TC1
≥
54°F
(
12°C
)
, TC2
≥
54°F
(
12°C
)
and TCJ
≥
54°F
(
12°C
)
2)
After 20 minutes elapsed from the stop.
- 17 -