16
Note 1)
When setting the line address from the wired remote controller, do not use address 29 and 30.
The address 29 and 30 cannot be set up in the outdoor unit. Therefore if they are incorrectly set up, a check code
[E04] (Indoor/outdoor communication circuit error) is output.
Note 2)
When manual address has been set up from the wired remote controller, set up the following items for header unit of
each line if performing a central control over refrigerant lines.
• Using SW13 and 14 on the interface P.C. board of the header unit in each line, set up the line address for each line.
• Turn off SW30-2 on the interface P.C. boards of the header units of the lines connected to the identical central
control except a line with least address number.
(The terminal resistances of the cables in the central control system of indoor/outdoor are unified.)
• Connect the relay connector between [U1U2] and [U3U4] of the header unit for each refrigerant line.
• Then set up the central control address.
(For the central control address setup, refer to the Installation manual of the central control devices.)
Confirmation of indoor address and the main unit position on the remote controller
[Confirmation of indoor unit No. and position]
1. When you want to know the indoor address though position of the indoor unit itself can be
recognized;
• In case of individual operation (Wired remote controller : Indoor unit = 1 : 1) or group control
<Procedure> (Operation while the air conditioner operates)
1
If it stops, push
button.
2
Push
UNIT
button.
The unit NO
1-1
is displayed on the LCD. (Disappears after several seconds) The displayed unit No indicates
the line address and indoor address. (If there is other indoor unit connected to the same remote controller (Group
control unit), other unit No is displayed every pushing
UNIT
button.)
Operation procedure
1 2
Operate
UNIT
SET
CL
UNIT No.
2
1