(Example)
Address setup procedure
Wire systematic diagram
In case of central control in a single refrigerant line
To procedure 1
In case of central control over refrigerant lines
To procedure 2
Address setup procedure 1
Turn on power of indoor/outdoor units.
(In order of indoor
→
→
→
→
→
Outdoor)
After approx. 1 minute, check that U. 1. L08 (U. 1. flash) is
displayed in 7-segment display section on the interface P.C.
board of the header unit.
Push SW15 and start setup the automatic address.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
When the count Auto 1
→
Auto 2
→
Auto 3 is displayed in
7-segment display section, and it changes from
U. 1. - - - (U. 1. flash) to
U. 1. - - - (U. 1. light) , the setup finished.
When perform a central control, connect a relay connector
between [U1U2] of the header unit and [U3U4] terminals.
Outdoor
Indoor
Indoor
Remote
controller
Remote
controller
Central remote
controller
Outdoor
Indoor
Indoor
Remote
controller
Central remote
controller
Outdoor
Indoor
Indoor
Remote
controller
Remote
controller
Outdoor
Indoor
Indoor
Remote
controller
Central remote
controller
7
ADDRESS SETUP
In this air conditioner, it is necessary to set up the indoor address before starting the operation.
Set up the address in the following procedure.
CAUTION
1. Set up address after wiring work.
2. Be sure to turn on the power in order of indoor unit
→
outdoor unit. If turning on the power in the reverse
order, a check code [E19] (Error of No. of header units) is output. When a check code is output, turn on the
power again.
3. It requires maximum 10 minutes (Usually, approx. 5 minutes) to set up automatically an address to 1 line.
4. To set up an address automatically, the setup at outdoor side is necessary.
(Address setup cannot be performed by power-ON only.)
5. To set up an address, it is unnecessary to operate the air conditioner.
6. Manual address setup is also available besides automatic setup.
Automatic address : Setup from SW15 on the interface P.C. board of the header unit
Manual address
: Setup from the weird remote controller
*
It is temporarily necessary to set the indoor unit and wired to 1 : 1.
(In group operation and in time without remote controller)
Automatic Address Setup
Without central control : To the address setup procedure 1
With central control
: To the address setup procedure 2
(However, go to the procedure 1 when the central control is performed in a single refrigerant line.)
SW04
SW01
1
SW05 SW15
D600 D601 D602 D603 D604
1
1
SW02 SW03
3
5
2 4
Header unit interface P.C. board
U1 U2
For internal
wiring between
indoor and
outdoor
U3 U4
For wiring of
central control
system
U5 U6
For internal
wiring between
outdoor units