In case of test operation on the interface P.C. board of the header outdoor unit
This air conditioner has a function which executes a test operation by operation of the switches on the interface P.C.
board of the header unit.
This function is classified into “Individual test operation” which performs a test operation individually in each indoor
unit and “Collective test operation” which performs a test operation for all the connected indoor units.
<Individual test operation>
Start
operation
Stop
operation
Procedure
1
2
3
1
Operation
Set operation mode on wired remote controller of the indoor
unit which is operated with test mode to [COOL] or [HEAT].
(When it is not set up, operate the air conditioner with the
current operation mode.)
Set the rotary switch SW01 on the interface P.C. board of the
header unit to [16], and match SW02 and SW03 to the
address of the indoor unit to be operated with test mode.
Push SW04 for 10 seconds or more.
• Operation mode changes to the operation mode of wired
remote controller of the corresponding indoor unit.
• Temperature cannot be adjusted during “Test operation”.
• Error is detected as usual.
• Test operation is not performed 3 minutes after power was
turned on or operation has stopped.
Return the rotary switches on the interface P.C. board of the
header unit, SW01 = [1], SW02 = [1], SW03 = [1].
<Collective test operation>
Start
operation
Stop
operation
Procedure
1
2
1
Operation
Set the rotary switches of interface P.C. board of the header unit;
COOL: SW01 = [2], SW02 = [5], SW03 = [1]
HEAT: SW01 = [2], SW02 = [6], SW03 = [1]
Push SW04 for 2 seconds or more.
• Temperature cannot be adjusted during “Test operation”.
• Error is detected as usual.
• Test operation is not performed 3 minutes after power was turned on
or operation has stopped.
Return the rotary switches on the interface P.C. board of the header
unit, SW01 = [1], SW02 = [1], SW03 = [1].
7-segment display
7-segment display
[A]
[U1]
[A]
[ ]
↓↓↓↓↓
Address display of the
corresponding indoor unit
[A]
[ ]
↓↓↓↓↓
Address display of the
corresponding indoor unit
[A]
[U1]
[B]
[ ]
[B]
[ ]
[B]
[ ]
↓↓↓↓↓
[FF] is displayed
for 5 seconds.
[B]
[ ]
[A]
[C ]
[H ]
[A]
[C ]
[H ]
[A]
[U1]
[B]
[ ]
[ ]
[B]
[ –C ]
[ –H ]
[B]
[ ]
Interface P.C. board
SW04 SW05 SW15
D600 D601 D602 D603 D604
SW03
1
SW02
1
SW01
1
SW06
1
ON
2 3 4
SW07
1
ON
ON
ON
ON
2 3 4
SW09
SW08
1
1
2 3 4
SW10
1 2 3 4
SW04 SW05 SW15
D600 D601 D602 D603 D604
SW03
1
Push switch
Push switch
7-segment
display [B]
7-segment
display [A]
Rotary switch
SW02
1
SW01
1