55
n
Einzelne Außeneinheit
Spannungsbereich
Verdichter
Lüftermotor
Stromversorgung
Modell mit
Heizung
MMY-
Modell nur
zur Kühlung
MMY-
Nennspannung
(V-Ph-Hz)
Min
Max
RLA
LRA
kW
FLA
MCA MOCP
ICF
MAP0501HT8 MAP0501T8
400-3-50
342
457
4.0 + 4.0
0.60
0.8
16.5
20
—
MAP0601HT8 MAP0601T8
400-3-50
342
457
4.6 + 4.6
0.60
0.8
16.5
20
—
MAP0801HT8 MAP0801T8
400-3-50
342
457
5.2 + 5.2
0.60
1.0
20.0
30
—
MAP1001HT8 MAP1001T8
400-3-50
342
457
6.5 + 6.5
0.60
1.1
22.5
30
—
MAP1201HT8 MAP1201T8
400-3-50
342
457
9.5 + 9.5
0.60
1.1
24.5
30
—
n
Einzelne Außeneinheit
Verdichter
Spannungsbereich
Einheit 1
Einheit 2
Einheit 3
Einheit 4
Lüftermotor
Stromversorgung
Modell mit
Heizung
MMY-
Modell nur
zur Kühlung
MMY-
Nennspannung
(V-Ph-Hz)
Min
Max
RLA
LRA
RLA
LRA
RLA
LRA
RLA
LRA
kW
FLA
MCA MOCP
ICF
AP1401HT8
AP1401T8
400-3-50
342
457
5.2 + 5.2
—
4.6 + 4.6
—
—
—
—
—
0.6 × 2 1.0 + 0.8
36.5
40
—
AP1601HT8
AP1601T8
400-3-50
342
457
5.2 + 5.2
—
5.2 + 5.2
—
—
—
—
—
0.6 × 2 1.0 + 1.0
40.0
50
—
AP1801HT8
AP1801T8
400-3-50
342
457
6.5 + 6.5
—
5.2 + 5.2
—
—
—
—
—
0.6 × 2 1.0 + 1.1
42.5
50
—
AP2001HT8
AP2001T8
400-3-50
342
457
6.5 + 6.5
—
6.5 + 6.5
—
—
—
—
—
0.6 × 2 1.1 + 1.1
45.0
60
—
AP2201HT8
AP2201T8
400-3-50
342
457
5.2 + 5.2
—
5.2 + 5.2
—
4.6 + 4.6
—
—
—
0.6 × 3 1.0 + 1.0 + 0.8
56.5
70
—
AP2211HT8
AP2211T8
400-3-50
342
457
9.5 + 9.5
—
6.5 + 6.5
—
—
—
—
—
0.6 × 2 1.1 + 1.1
47.0
60
—
AP2401HT8
AP2401T8
400-3-50
342
457
5.2 + 5.2
—
5.2 + 5.2
—
5.2 + 5.2
—
—
—
0.6 × 3 1.0 + 1.0 + 1.0
60.0
70
—
AP2411HT8
AP2411T8
400-3-50
342
457
9.5 + 9.5
—
9.5 + 9.5
—
—
—
—
—
0.6 × 2 1.1 + 1.1
49.0
60
—
AP2601HT8
AP2601T8
400-3-50
342
457
6.5 + 6.5
—
5.2 + 5.2
—
5.2 + 5.2
—
—
—
0.6 × 3 1.1 + 1.1 + 1.0
62.5
70
—
AP2801HT8
AP2801T8
400-3-50
342
457
6.5 + 6.5
—
6.5 + 6.5
—
5.2 + 5.2
—
—
—
0.6 × 3 1.1 + 1.1 + 1.0
65.0
80
—
AP3001HT8
AP3001T8
400-3-50
342
457
6.5 + 6.5
—
6.5 + 6.5
—
6.5 + 6.5
—
—
—
0.6 × 3 1.1 + 1.1 + 1.1
67.5
80
—
AP3201HT8
AP3201T8
400-3-50
342
457
5.2 + 5.2
—
5.2 + 5.2
—
5.2 + 5.2
—
5.2 + 5.2
—
0.6 × 4 1.0 + 1.0 + 1.0 + 1.0 80.0
90
—
AP3211HT8
AP3211T8
400-3-50
342
457
9.5 + 9.5
—
6.5 + 6.5
—
6.5 + 6.5
—
—
—
0.6 × 3 1.1 + 1.1 + 1.1
69.5
80
—
AP3401HT8
AP3401T8
400-3-50
342
457
6.5 + 6.5
—
5.2 + 5.2
—
5.2 + 5.2
—
5.2 + 5.2
—
0.6 × 4 1.1 + 1.0 + 1.0 + 1.0 82.5
100
—
AP3411HT8
AP3411T8
400-3-50
342
457
9.5 + 9.5
—
9.5 + 9.5
—
6.5 + 6.5
—
—
—
0.6 × 3 1.1 + 1.1 + 1.1
71.5
80
—
AP3601HT8
AP3601T8
400-3-50
342
457
6.5 + 6.5
—
6.5 + 6.5
—
5.2 + 5.2
—
5.2 + 5.2
—
0.6 × 4 1.1 + 1.1 + 1.0 + 1.0 85.0
100
—
AP3611HT8
AP3611T8
400-3-50
342
457
9.5 + 9.5
—
9.5 + 9.5
—
9.5 + 9.5
—
—
—
0.6 × 3 1.1 + 1.1 + 1.1
73.5
90
—
AP3801HT8
AP3801T8
400-3-50
342
457
6.5 + 6.5
—
6.5 + 9.5
—
6.5 + 6.5
—
5.2 + 5.2
—
0.6 × 4 1.1 + 1.1 + 1.1 + 1.0 87.5
100
—
AP4001HT8
AP4001T8
400-3-50
342
457
6.5 + 6.5
—
6.5 + 6.5
—
6.5 + 6.5
—
6.5 + 6.5
—
0.6 × 4 1.1 + 1.1 + 1.1 + 1.1 90.0
100
—
AP4201HT8
AP4201T8
400-3-50
342
457
9.5 + 9.5
—
6.5 + 6.5
—
6.5 + 6.5
—
6.5 + 6.5
—
0.6 × 4 1.1 + 1.1 + 1.1 + 1.1 92.0
110
—
AP4401HT8
AP4401T8
400-3-50
342
457
9.5 + 9.5
—
9.5 + 9.5
—
6.5 + 6.5
—
6.5 + 6.5
—
0.6 × 4 1.1 + 1.1 + 1.1 + 1.1 94.0
110
—
AP4601HT8
AP4601T8
400-3-50
342
457
9.5 + 9.5
—
9.5 + 9.5
—
9.5 + 9.5
—
6.5 + 6.5
—
0.6 × 4 1.1 + 1.1 + 1.1 + 1.1 96.0
110
—
AP4801HT8
AP4801T8
400-3-50
342
457
9.5 + 9.5
—
9.5 + 9.5
—
9.5 + 9.5
—
9.5 + 9.5
—
0.6 × 4 1.1 + 1.1 + 1.1 + 1.1 98.0
110
—
HINWEIS :
Legende
MCA
MOCP
ICF
RLA
: Min. Stromstärke im Stromkreis (A)
: Max. Überstromschutz (A)
: Max. Stromaufnahme Start
: Nennlast (A)
LRA
FLA
kW
: Kurzschlussstrom
: Volllast (A)
: Nennleistung Ventilatormotor (kW)
RLA basiert auf folgende Bedienungen
Raumtemperatur
: 27° C TKT/19° C FKT
Außentemperatur
: 35° C TKT
50Hz
6
ELEKTRISCHE VERDRAHTUNG
Содержание MAP0601HT7