13
No.
Piping parts
Outdoor unit
↓
T-shape
branching joint
Between T-shape
branching joints
T-shape joint of
header unit
↓
1st branching
section
Branching section
↓
Branching section
Branching section
↓
Indoor unit
Name
Outdoor unit
connecting pipe
Main connecting
piping between of
outdoor units
Balance pipe
Main piping
Branching pipe
Indoor unit
connecting pipe
Selection of pipe size
1) Connecting pipe outdoor unit
Model
MMY-MAP0501H
MMY-MAP0601H
MMY-MAP0801H
MMY-MAP1001H
MMY-MAP1201H
Gas side
Ø15.9
Ø19.1
Ø22.2
Ø22.2
Ø28.6
Liquid side
Ø9.5
Ø9.5
Ø12.7
Ø12.7
Ø12.7
2) Pipe size for connecting piping between outdoor units
Total capacity codes of outdoor
units at downstream side
Equivalent
Equivalent
to capacity
to HP
Below 38.4
Below 14
38.4 to below 61.5
14 to below 22
61.5 to below 73.0
22 to below 26
73.0 to below 96.0
26 to below 36
Above 101.0
Above 36
Gas
side
Ø28.6
Ø28.6
Ø34.9
Ø34.9
Ø41.3
Liquid
side
Ø12.7
Ø15.9
Ø15.9
Ø19.1
Ø22.2
Balance
pipe
Ø9.5
3) Size of main piping
Total capacity codes of all outdoor units
Equivalent
Equivalent
to capacity
to HP
Below 16.0
Below 6
16.0 to below 22.4
6 to below 8
22.4 to below 33.5
8 to below 12
33.5 to below 38.4
12 to below 14
38.4 to below 61.5
14 to below 22
61.5 to below 73.0
22 to below 26
73.0 to below 101.0
26 to below 36
101.0 to below 118.0
36 to below 46
Above 118.0
Above 46
Gas side
Ø15.9
Ø19.1
Ø22.2
Ø28.6
Ø28.6
Ø34.9
Ø34.9
Ø41.3
Ø41.3
∗
Liquid side
Ø9.5
Ø9.5
Ø12.7
Ø12.7
Ø15.9
Ø15.9
Ø19.1
Ø22.2
Ø22.2
∗
Max. equivalent length of main pipe is below 70m.
4) Pipe size between branching sections
Total capacity codes of indoor units
at downstream side
Equivalent
Equivalent
to capacity
to HP
Below 7.5
Below 2.8
7.5 to below 18.0
2.8 to below 6.4
18.0 to below 34.0
6.4 to below 12.2
34.0 to below 56.5
12.2 to below 20.2
∗
56.5 to below 70.5
20.2 to below 25.2
1
70.5 to below 98.5
25.2 to below 35.2
98.5 to below 118.5
35.2 to below 42.2
Above 118.5
Above 42.2
Gas side
Ø12.7
Ø15.9
Ø22.2
Ø28.6
Ø34.9
Ø34.9
Ø41.3
Ø41.3
Liquid side
Ø9.5
Ø9.5
Ø12.7
Ø15.9
Ø15.9
Ø19.1
Ø22.2
Ø22.2
5) Connecting pipe size of indoor unit
Capacity rank
007 to 012 type (15m or less)
007 to 012 type (15m or more)
015 to 018 type
024 to 048 type
056 type
072 type
096 type
Gas side
Ø9.5
Ø12.7
Ø12.7
Ø15.9
Ø15.9
Ø19.1
Ø22.2
Liquid side
Ø6.4
Ø6.4
Ø6.4
Ø9.5
Ø9.5
Ø12.7
Ø12.7
Remarks
Same to connecting pipe
size of outdoor unit
Pipe size differs based on
total capacity code value of
outdoor units at
downstream side.
(See Table 2.)
Pipe size differs based on
capacity code of outdoor
unit.
(See Table 2.)
Pipe size differs based on
total capacity code value of
indoor units at downstream
side.
If the total value exceeds
the capacity code of the
outdoor unit, apply capacity
code of the outdoor unit.
(See Table 1.2.)
∗
1: If exceeding the main pipe size, decide the size same to
main pipe size.
5
REFRIGERANT PIPING