7
6
ELECTRIC WIRING
n
Single outdoor unit
Voltage
Range
Compressor
Fan Motor
Power Supply
Heat Pump
Model
MMY-
Cooling
Only model
MMY-
Nominal
Voltage
(V-Ph-Hz)
Min
Max
RLA
LRA
kW
FLA
MCA MOCP
ICF
MAP0501HT8 MAP0501T8 400-3-50
342
457
4.0 + 4.0
0.60
0.8
16.5
20
—
MAP0601HT8 MAP0601T8 400-3-50
342
457
4.6 + 4.6
0.60
0.8
16.5
20
—
MAP0801HT8 MAP0801T8 400-3-50
342
457
5.2 + 5.2
0.60
1.0
20.0
30
—
MAP1001HT8 MAP1001T8 400-3-50
342
457
6.5 + 6.5
0.60
1.1
22.5
30
—
MAP1201HT8 MAP1201T8 400-3-50
342
457
9.5 + 9.5
0.60
1.1
24.5
30
—
n
Combination of outdoor unit
Compressor
Voltage
Range
Unit No.1
Unit No.2
Unit No.3
Unit No.4
Fan Motor
Power Supply
Heat Pump
Model
MMY-
Cooling
Only model
MMY-
Nominal
Voltage
(V-Ph-Hz)
Min
Max
RLA
LRA
RLA
LRA
RLA
LRA
RLA
LRA
kW
FLA
MCA MOCP
ICF
AP1401HT8
AP1401T8
400-3-50
342
457
5.2 + 5.2
—
4.6 + 4.6
—
—
—
—
—
0.6 × 2 1.0 + 0.8
36.5
40
—
AP1601HT8
AP1601T8
400-3-50
342
457
5.2 + 5.2
—
5.2 + 5.2
—
—
—
—
—
0.6 × 2 1.0 + 1.0
40.0
50
—
AP1801HT8
AP1801T8
400-3-50
342
457
6.5 + 6.5
—
5.2 + 5.2
—
—
—
—
—
0.6 × 2 1.0 + 1.1
42.5
50
—
AP2001HT8
AP2001T8
400-3-50
342
457
6.5 + 6.5
—
6.5 + 6.5
—
—
—
—
—
0.6 × 2 1.1 + 1.1
45.0
60
—
AP2201HT8
AP2201T8
400-3-50
342
457
5.2 + 5.2
—
5.2 + 5.2
—
4.6 + 4.6
—
—
—
0.6 × 3 1.0 + 1.0 + 0.8
56.5
70
—
AP2211HT8
AP2211T8
400-3-50
342
457
9.5 + 9.5
—
6.5 + 6.5
—
—
—
—
—
0.6 × 2 1.1 + 1.1
47.0
60
—
AP2401HT8
AP2401T8
400-3-50
342
457
5.2 + 5.2
—
5.2 + 5.2
—
5.2 + 5.2
—
—
—
0.6 × 3 1.0 + 1.0 + 1.0
60.0
70
—
AP2411HT8
AP2411T8
400-3-50
342
457
9.5 + 9.5
—
9.5 + 9.5
—
—
—
—
—
0.6 × 2 1.1 + 1.1
49.0
60
—
AP2601HT8
AP2601T8
400-3-50
342
457
6.5 + 6.5
—
5.2 + 5.2
—
5.2 + 5.2
—
—
—
0.6 × 3 1.1 + 1.1 + 1.0
62.5
70
—
AP2801HT8
AP2801T8
400-3-50
342
457
6.5 + 6.5
—
6.5 + 6.5
—
5.2 + 5.2
—
—
—
0.6 × 3 1.1 + 1.1 + 1.0
65.0
80
—
AP3001HT8
AP3001T8
400-3-50
342
457
6.5 + 6.5
—
6.5 + 6.5
—
6.5 + 6.5
—
—
—
0.6 × 3 1.1 + 1.1 + 1.1
67.5
80
—
AP3201HT8
AP3201T8
400-3-50
342
457
5.2 + 5.2
—
5.2 + 5.2
—
5.2 + 5.2
—
5.2 + 5.2
—
0.6 × 4 1.0 + 1.0 + 1.0 + 1.0
80.0
90
—
AP3211HT8
AP3211T8
400-3-50
342
457
9.5 + 9.5
—
6.5 + 6.5
—
6.5 + 6.5
—
—
—
0.6 × 3 1.1 + 1.1 + 1.1
69.5
80
—
AP3401HT8
AP3401T8
400-3-50
342
457
6.5 + 6.5
—
5.2 + 5.2
—
5.2 + 5.2
—
5.2 + 5.2
—
0.6 × 4 1.1 + 1.0 + 1.0 + 1.0
82.5
100
—
AP3411HT8
AP3411T8
400-3-50
342
457
9.5 + 9.5
—
9.5 + 9.5
—
6.5 + 6.5
—
—
—
0.6 × 3 1.1 + 1.1 + 1.1
71.5
80
—
AP3601HT8
AP3601T8
400-3-50
342
457
6.5 + 6.5
—
6.5 + 6.5
—
5.2 + 5.2
—
5.2 + 5.2
—
0.6 × 4 1.1 + 1.1 + 1.0 + 1.0
85.0
100
—
AP3611HT8
AP3611T8
400-3-50
342
457
9.5 + 9.5
—
9.5 + 9.5
—
9.5 + 9.5
—
—
—
0.6 × 3 1.1 + 1.1 + 1.1
73.5
90
—
AP3801HT8
AP3801T8
400-3-50
342
457
6.5 + 6.5
—
6.5 + 9.5
—
6.5 + 6.5
—
5.2 + 5.2
—
0.6 × 4 1.1 + 1.1 + 1.1 + 1.0
87.5
100
—
AP4001HT8
AP4001T8
400-3-50
342
457
6.5 + 6.5
—
6.5 + 6.5
—
6.5 + 6.5
—
6.5 + 6.5
—
0.6 × 4 1.1 + 1.1 + 1.1 + 1.1
90.0
100
—
AP4201HT8
AP4201T8
400-3-50
342
457
9.5 + 9.5
—
6.5 + 6.5
—
6.5 + 6.5
—
6.5 + 6.5
—
0.6 × 4 1.1 + 1.1 + 1.1 + 1.1
92.0
110
—
AP4401HT8
AP4401T8
400-3-50
342
457
9.5 + 9.5
—
9.5 + 9.5
—
6.5 + 6.5
—
6.5 + 6.5
—
0.6 × 4 1.1 + 1.1 + 1.1 + 1.1
94.0
110
—
AP4601HT8
AP4601T8
400-3-50
342
457
9.5 + 9.5
—
9.5 + 9.5
—
9.5 + 9.5
—
6.5 + 6.5
—
0.6 × 4 1.1 + 1.1 + 1.1 + 1.1
96.0
110
—
AP4801HT8
AP4801T8
400-3-50
342
457
9.5 + 9.5
—
9.5 + 9.5
—
9.5 + 9.5
—
9.5 + 9.5
—
0.6 × 4 1.1 + 1.1 + 1.1 + 1.1
98.0
110
—
NOTE :
Legend
MCA
MOCP
ICF
RLA
: Minimum Circuit Amps
: Maximum Overcurrent Protection (Amps)
: Maximum Instantaneous Current Flow Start
: Rated Load Amps
LRA
FLA
kW
: Locked Rotor Amps
: Full Load Amps
: Fan Motor Rated Output (kW)
RLA is based on the following conditions.
Indoor temperature
: 27°C DB/19°C WB
Outdoor temperature : 35°C DB
50Hz
Содержание MAP0601HT7
Страница 61: ...EH99834001 ...