6 F 8 A 0 9 3 4
5.3 Notes on Wiring
Notes on Instrumentation-Converter Wiring
•
To avoid 2-point grounding,
ground the shield of output cable basically at the receiving side.
•
Use a grounding wire of IV wire 5.5mm
2
or more. The size of the external grounding terminal screws is M4.
Do not share
a grounding wire with other instruments where grounding current may flow. (An
independent grounding is preferable.)
•
Power cable
When a 3-core cable is used:
Ground with the FG terminal.
When a 2-core cable is used: Use an external grounding terminal and make the cable as short as possible.