10.9 Multiple range high/low limit alarm function (option)
The procedure to use multiple range high/low limit alarm is shown below.
Range setting
・
Set the range in accordance with
8.2.9 Span (range)
in the following order.
1. Set the range type to “
unidirectional flow, multiple ranges selected by
external signal
”.
2. Set Range 1 and Range 2 respectively.
DO setting (Note 1)
・
Set digital output 1 and 2 (
DO1
,
DO2
) function to
multiple range high limit
alarm output and multiple range low limit alarm output
respectively in
accordance with
8.2.18 Digital I/O
.
Also set the alarm output state to either of
normally open
or
normally close
.
DI
setting
・
Set digital input (
DI
) function to
RANGE SW
in accordance with
8.2.19
Digital I/O
.
High/Low limit
alarm value setting
・
Set
high limit alarm and low limit alarm
to
ON
and set alarm value to high
and low alarms respectively in accordancewith
8.2.23 Flow Rate High, Low,
High-High and Low-Low limit Alarm Setting
.
Set the alarm not to use to OFF.
High High/Low Low limit
alarm value setting
・
Set
high-high alarm and low-low alarm to ON
and set alarm value to them
respectively in accordance with
8.2.23 Flow Rate High, Low, High-High
and Low-Low limit Alarm Setting
.
Set the alarm not to use to OFF.
(Note 1)
When setting DO using HHT AF900 (Ver2.40 or older)
, set alarm outputs
as below:
Multiple range high limit alarm output
SPECIAL-B,
Multiple range low limit alarm output
SPECIAL-A