System Installation
– Set Up Examples
1 Zone Heating
Equipment Required:
DPSW Settings:
DPSW11_2 = ON: Hot water cylinder electric heater disables
DPSW12_1 = ON: Hot water cylinder not connected to system
All other DPSW’s set in the OFF position.
Function Code Settings:
Please check the following pages for the set-up of:
External room thermostat
pg.40
Room temperature controller (HWS-AMS11-E)
pg.41
Auto curve set up
pg.43
Note: Care should be taken when setting FC1A if the heating emitter used for Zone 1 is under floor
heating. If FC1A is set to high there is a risk that the floor surface could be damaged.
FC No
FC Description
FC Range
Default Setting
1A
Heating
– upper temperature set point limit - Zone 1( °C)
37 ~ 55
55
1B
Heating
– lower temperature set point limit - Zone 1( °C)
20 ~ 37
20