16
Control parts specifications
Component
Power
Current (Max)
Specification
3 way diverting valve
AC 230V
100mA
Default: 2 wire spring return valve or 3 wire SPST
valve
Option: 3 wire SPDT valve (set DPSW13_1 to ON)
2 way valve (cooling )
AC 230V
100mA
2 wire spring return valve (normally OPEN)
3 way mixing valve (2 zone
control)
AC 230V
100mA
Default drive time = 60 seconds to 90°
3 wire SPST or SPDT with drive times to 90° between
30 and 240 seconds
Output line specifications
Description
Output
Current
(Max)
Voltage
(Max)
Cable
Length
(Max)
Comments
External water
pump (P2)
AC230V
1A
-
12m
External booster
heater
AC230V
1A
-
12m
Output enabled when outdoor air
temperature is
≤ -20°C
Alarm output
No volt contacts
0.5A
AC230V
12m
1A
DC24V
12m
Boiler output
No volt contacts
0.5A
AC230V
12m
Output enabled when outdoor air
temperature is ≤ -10°C (output trigger
temperature can be changed using FC23)
1A
DC24V
12m
Defrost output
No volt contacts
0.5A
AC230V
12m
1A
DC24V
12m
Compressor ON
output
No volt contacts
0.5A
AC230V
12m
1A
DC24V
12m
Input line specifications
Description
Input
Cable Length (Max)
External stop control
No voltage
12m
Cylinder thermostat
No voltage
12m
Room thermostat (cooling)
No voltage
12m
Room thermostat (heating)
No voltage
12m