206
H9 ASD Installation and Operation Manual
Point 2 Frequency
Program
Communications
Communication Reference Adjust
This parameter is used to set the gain and bias of the
Communications
Reference
speed control input.
See
F811
for more information on this setting.
This parameter sets the
Communications Reference Speed Setpoint 2
.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F814
Parameter Type —
Numerical
Factory Default —
60.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
(
F011
)
Units — Hz
Baud Rate (RS485)
Program
Communications
Communication Settings
This parameter sets the RSRS485 baud rate.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
0 — 9600 bps
1 — 19200 bps
2 — 38400 bps
Direct Access Number — F820
Parameter Type —
Selection List
Factory Default —
19200
Changeable During Run —
Yes
RS485 Send Wait Time (RS485)
Program
Communications
Communication Settings
This parameter sets the
RS485
response delay time.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F825
Parameter Type —
Numerical
Factory Default — 0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
F814
F825