H9 ASD Installation and Operation Manual
39
Command Control Selections
The following is a listing with descriptions of the
Command Mode
(
F003
) selections (Program
Fundamental
Standard Mode Selection
Command Mode Selection
).
Settings:
0 — Terminal Block
Allows for
Command
control input via the
Terminal Board
.
1 — Not Used
Unused.
2 — EOI (Keypad)
Used for EOI command control.
3 — RS485
Used to transfer commands to the ASD via 4-wire RS485.
4 — Communication Option Board
Use this setting if using the optional
Communication Board
for command control.
Frequency Control
Selections
The following is a listing with descriptions of the
Frequency Mode
(
F004
) selections (Program
Fundamental
Standard Mode Selection
Frequency Mode 1
).
Settings:
1 — V/I
Used when a 0 to 10 VDC analog input or a 0 –
20 mADC current input is used as the speed control input. Only one input signal type may be
used at a time. Set
SW301
to the desired signal type.
2 — RR
Used for a 0 to 10 VDC analog input signal.
3 — RX
Used for a -10 to +10 VDC analog input signal.
4 — Not Used
Unused.
5 — EOI (Keypad)
Used for EOI frequency control.
6 — RS485
Used to transfer speed commands to the ASD via 4-wire RS485.
(Default)
(Default)