164
H9 ASD Installation and Operation Manual
Permanent Magnet (PM) Motor Constant 1
Program
Motor
PM Motor
This parameter is used with synchronous motor applications only.
Contact the TIC Customer Support Center for information on this parameter.
Direct Access Number — F498
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Units — %
Permanent Magnet (PM) Motor Constant 2
Program
Motor
PM Motor
This parameter is used with synchronous motor applications only.
Contact the TIC Customer Support Center for information on this parameter.
Direct Access Number — F499
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Units — %
Acceleration Time 2
Program
Special
Acc/Dec 1 – 4 Settings
This parameter specifies the time in seconds for the output of the ASD to go
from 0.0 Hz to the
Maximum Frequency
for the
2 Acceleration
profile. The
Accel/Decel pattern may be set using
F502
. The minimum Accel/Decel time
may be set using
F508
.
This setting is also used to determine the acceleration rate of the
UP/DOWN
Frequency Functions
.
Note:
An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic
Accel/Decel
,
Stall
, and
Ridethrough
settings
may lengthen the
acceleration times.
Direct Access Number — F500
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds
Deceleration Time 2
Program
Fundamental
Accel/Decel 1 Settings
This parameter specifies the time in seconds for the output of the ASD to go
from the
Maximum Frequency
to 0.0 Hz for the
2 Deceleration
profile. The
Accel/Decel pattern may be set using
F502
. The minimum Accel/Decel time
may be set using
F508
.
This setting is also used to determine the deceleration rate of the
UP/DOWN
Frequency Functions
.
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic
Accel/Decel
,
Stall
, and
Ridethrough
settings
may lengthen the
deceleration times.
Direct Access Number — F501
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
F498
F501